| 2021-03-02 17:27:35 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20110707 2ND CYCLE |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | SEPARATE PERMITS AND REVIEWS ARE REQUIRED FOR THE |
| | KITCHEN HOODS AND THE REFRIGERATION EQUIPMENT. |
| | |
| | |
| | 1) PLEASE PROVIDE A LETTER SHOWING A CHANGE OF EOR. |
| | |
| | 2) SHEET M-501: PLEASE CHECK LABELING OF DUCTWORK FOR |
| | DETAIL (2) AS IT APPEARS THE OUTDOOR AIR IS LABELED SA, |
| | AND IT APPEARS THAT SA IS DUCTED INTO EACH RA. FBC |
| | 107.2.1 |
| | |
| | 3) OUTDOOR AIR CALCULATIONS MUST BE CALCULATED |
| | ACCORDING TO TABLE 403.3.1.1 NOT BY THE OCCUPANCY SHOWN |
| | IN THE ARCHITECTURAL DRAWINGS. FBC M 403.3.1.1 |
| | |
| | 4) SHEET M-702: PLEASE PROVIDE A COMPLETE OUTDOOR AIR |
| | CALCULATION CHART, THERE APPEARS TO BE SEVERAL SPACES |
| | IN THIS BUILDING THAT DO NOT APPEAR IN THE VENTILATION |
| | RATE CALCULATIONS. FBC M 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |