| 2021-03-04 15:17:06 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20110707 |
| | 3/4/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P503 GAS ISOMETRIC: |
| | |
| | A) PLEASE LABEL THE REGULATORS AND SHOW THE OUTLET |
| | PRESSURES- SECTION 410.1 FBC FG. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS MARKED UP TO SHOW THE INLET AND OUTLET |
| | PRESSURE PIPE SIZES AND PRESSURES. |
| | |
| | B) SHOW THE LOCATION OF THE AUTO GAS VALVE FOR THE FIRE |
| | SUPPRESSION SYSTEM- SEC.10.4.1 NFPA 96. |
| | |
| | 2) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING |
| | APPLIANCES- SECTION 304.1 FBC FG. INDICATE WHICH METHOD |
| | WILL BE USED TO SUPPLY THE AIR. |
| | |
| | 3) PROVIDE VENTING PLANS AND SPECIFICATIONS FOR THE FOR |
| | THE WATER HEATERS- SECTIONS 505 7 503 FBC FG. |
| | |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING |
| | APPLIANCES AND WATER HEATERS- SECTIONS 623.1 AND 624.1 |
| | FBC FG. PLEASE INCLUDE THE SPECS FOR THE DIRECT VENT |
| | AIR INTAKE AND EXHAUST SYSTEM FOR THE WATER HEATER AS |
| | SHOWN ON SHEET M102. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |