| Plan Review Notes For Permit 20110707 |
| Permit Number |
20110707 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-05 12:37:20 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) REVISED 2ND FLOOR EXIT ACCESS USING THE PIAZZA - | | | PLEASE SHOW THE WIDTH OF THE PIAZZA AND ADDED DOOR TO | | | COMPLY WITH FBC 1005.4 CONTINUITY. | | | THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE MEANS OF | | | EGRESS REQUIRED FROM ANY STORY OF A BUILDING SHALL NOT | | | BE REDUCED ALONG THE PATH OF EGRESS TRAVEL UNTIL | | | ARRIVAL AT THE PUBLIC WAY. | | | | | | PROVISO: (EXTERIOR DESIGN OF ROOF TOP BAR WALLS AND | | | OVERHEAD DOOR WILL NEED TO MEET WIND LOADS (FBC 1609) | | | WITH GLAZING TO MEET IMPACT LOADS (FBC 1609.1.2) ) | | | | | | |
|