| 2020-12-07 15:38:03 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110707 |
| | 12/7/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-000: |
| | |
| | A) PROVIDE A LIST OF SEPARATELY PERMITTED ITEMS |
| | INCLUDING THE WATER SERVICE BACKFLOW PREVENTER, GREASE |
| | INTERCEPTOR, GAS PIPING, GENERATOR, AND THE IRRIGATION |
| | SYSTEM. PLEASE NOTE COMPLETE SETS OF PLANS AND |
| | SPECIFICATIONS ARE REQUIRED FOR REVIEW- SECTION 107.2.1 |
| | WPB. |
| | |
| | B) PROVIDE A LIST OF DEFERRED SUBMITTALS INCLUDING THE |
| | FOOD SERVICE EQUIPMENT PLANS, AND ALL PLUMBING |
| | FIXTURES, APPLIANCES, DEVICES, AND EQUIPMENT |
| | SPECIFICATIONS NOT TO BE SUBMITTED UNDER THIS MAIN |
| | PERMIT- SECTION 107.3.4.1 WPB. |
| | |
| | 2) THERE ARE TWO P-101 PLANS IN THIS SUBMITTAL- ONE |
| | FROM THE PREVIOUS ENGINEER AND ONE FROM THE NEW |
| | ENGINEER. PLEASE RENAME ONE OF THESE SHEETS- SECTION |
| | 107.2.1 WPB. |
| | |
| | 3) P-000: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| | COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE |
| | THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF |
| | FIXTURES. |
| | |
| | 4) P-001: THIS PLAN SHEET IS NOT IN THE INDEX ON P-000. |
| | PLEASE ADD IT TO THE INDEX AND REVISE THE FIXTURE AND |
| | EQUIPMENT SCHEDULES ON THE PLAN TO MATCH THE SCHEDULES |
| | ON P701- SECTION 107.2.1 WPB. |
| | |
| | 5) SHEETS A0.04 & P101: PLEASE PROVIDE THE CIVIL, PLANS |
| | THAT ARE REFERENCED IN THE NOTES AND OTHER PLAN SHEET |
| | NOTES FOR CONTINUATIONS OF THE PLUMBING AND STORM DRAIN |
| | PIPING SYSTEMS- SECTION 107.2.1. |
| | |
| | 6) ELLIS AND GRITTER P101: REVISE THE GREASE WASTE |
| | PIPING LAYOUT TO MATCH THE NEW LAYOUT SHOWN ON SHEETS |
| | P401 & 501- SECTION 107.2.1 WPB. BOTH THE OLD AND NEW |
| | P101 PLAN SHEETS AND P401 & P501 SHOW THE MOP SINK |
| | DRAIN CONNECTING TO THE GREASE WASTE LINE, PLEASE NOTE |
| | IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE MOP SINK |
| | SHALL DRAIN INTO THE SANITARY AND NOT INTO THE GREASE |
| | WASTE LINE. |
| | |
| | 7) P101 & P701 GREASE INTERCEPTOR: AS NOTED IN COMMENT |
| | #1A A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE |
| | GREASE INTERCEPTOR, AND THE SUBMITTAL SHALL INCLUDE THE |
| | FOLLOWING LIST OF ITEMS. |
| | |
| | A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | MANUAL FOR THE SCHIER INTERCEPTOR WITH APPROVAL STAMPS |
| | BY THE EOR. |
| | |
| | B) REVISED SIZING CALCULATIONS. PLEASE NOTE THE CURRENT |
| | EQUIPMENT SCHEDULE SEEMS TO INDICATE TWO DIFFERENT |
| | SIZING METHODS- THE PDI METHOD WHICH IS BASED ON GPM |
| | FLOW-THRU RATINGS AND GREASE RETENTION TIME FOR THE |
| | FIXTURES, AND FAC RULE 64E-6.013 METHOD WHICH IS BASED |
| | ON THE NUMBER OF SEATS, GALLONS OF WASTEWATER ETC.- |
| | THIS METHOD IS COMMONLY USED FOR GRAVITY-TYPE |
| | INTERCEPTORS. |
| | |
| | 8) P101, P601. P701 SUMP PUMP AND PIT. |
| | |
| | A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SUMP |
| | PUMP. SECTION 712.3.1 FBC P. THE PUMP SHALL BE EQUIPPED |
| | WITH AN OIL WATER SEPARATOR OR IT SHALL BE PROVIDED |
| | SEPARATELY- SECTION 1003.4 FBC P. |
| | |
| | B) PROVIDE THE DIMENSIONS OF THE SUMP PIT IN THE |
| | DETAIL- SECTION 712.3.2. |
| | |
| | C) PROVIDE A GAS TIGHT COVER FOR THE SUMP PIT- SECTION |
| | 712.3.2. |
| | |
| | D) PROVIDE THE SIZE OF THE DISCHARGE PIPING AND PROVIDE |
| | A VENT FOR THE PIT- SECTION 713.2.1. |
| | |
| | 9) P101 & P102: NOTE #8 (P102) INDICATES CLEANOUTS AT |
| | THE BASE OF SANITARY STACKS WHICH ARE NOT SHOWN ON AT |
| | THE CHASE LOCATION BY THE RESTROOMS. PLEASE NOTE THAT |
| | SECTION 1101.8 REQUIRES STORM DRAIN CLEANOUTS TO BE |
| | INSTALLED IN ACCORDANCE WITH THE CODES FOR SANITARY |
| | DRAIN CLEANOUTS. |
| | |
| | 10) P103, NOTE 306: ACCORDING TO SECTION 1104.2 FBC P |
| | FLOOR DRAINS SHALL NOT BE CONNECTED TO STORM DRAINS. |
| | PLEASE PROVIDE MORE INFORMATION AND DETAILS TO CLARIFY- |
| | SECTION 107.2.1 WPB. |
| | |
| | 11) P103: PROVIDE PRODUCT SUBMITTALS FOR RD-2, FD-1, |
| | AND TD-1. PLEASE CLARIFY IF THE FD-1 AND TD-1 SHOWN IN |
| | THE P701 SCHEDULE FOR THE INTERIOR ARE THE SAME TYPE OF |
| | FIXTURES TO BE INSTALLED IN THE EXTERIOR OPEN ROOF |
| | AREAS- SECTION 1105.1 FBC P AND SECTION 107.2.1 WPB. |
| | |
| | 12) P103: FD-1 ON THE LOWER ROOF SHALL NOT CONNECT TO |
| | THE SANITARY PER SEC. 90-126 WPB CODE OF ORDINANCES. |
| | |
| | 13) P103 & P503: REFER TO SECTION 1107.1 FBC P AND |
| | VERIFY THE ROOFS ARE DESIGNED FOR THE MAXIMUM POSSIBLE |
| | DEPTH OF WATER THAT WILL POND THEREON AS DETERMINED BY |
| | THE RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS, |
| | SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION |
| | WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING |
| | THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF |
| | DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED. THE |
| | MAXIMUM POSSIBLE DEPTH OF WATER ON THE ROOF SHALL |
| | INCLUDE THE HEIGHT OF THE WATER REQUIRED ABOVE THE |
| | INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO ACHIEVE |
| | THE REQUIRED FLOW RATE OF THE SECONDARY DRAINAGE MEANS |
| | TO ACCOMMODATE THE DESIGN RAINFALL RATE AS REQUIRED BY |
| | SECTION 1106. |
| | |
| | 14) P103, P104 & P503: PROVIDE SECONDARY OR EMERGENCY |
| | OVERFLOW ROOF DRAIN SYSTEMS INCLUDING CALCULATIONS AND |
| | OVERFLOW DRAIN DETAILS- SEE SECTION 1108 FBC P. |
| | |
| | 15) P503: PROVIDE A CONDENSATE DISPOSAL RISER- SECTION |
| | 107.2.1 WPB. |
| | |
| | 16) P401 SANITARY A: SEE COMMENT #7. |
| | |
| | 17) P401, SANITARY C: IT APPEARS A CLEANOUT IS MISSING |
| | FOR THE 4 IN. GREASE WASTE BRANCH LINE IN THE KITCHEN |
| | BY THE DISHWASHER- SECTION 708.1.4 FBC P. CLARIFY HOW |
| | ACCESS TO THE WCO IN THE FREEZER WILL BE PROVIDED- |
| | SECTIONS 708.1.9 & 708.1.0 FBC P. |
| | |
| | 18) P501, SANITARY D: PROVIDE CLEANOUTS AT THE BASES OF |
| | THE 3 IN. STACKS. |
| | |
| | 19) P601: PLEASE PROVIDE INDIRECT WASTE PLUMBING PIPING |
| | DETAILS FOR THE 2 AND 3-COMPARTMENT SINKS, THE |
| | DISHWASHER, AND ALL OTHER DISHWASHING SINKS AND FOOD |
| | HANDLING EQUIPMENT OR FIXTURES- REFER TO SECTIONS |
| | 802.1, 802.1.1, 802.1.7, 802.1.8, AND 802.2 FBC P. |
| | |
| | 20) P701: THE 2 AND 3-COMPARTMENT SINKS APPEAR TO BE |
| | MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB. |
| | |
| | 21) P701: ITEM #35 WHICH IS REFERENCED IN ITEM #36 & 37 |
| | IS MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB. |
| | |
| | 22) P201: SHOW THE LOCATIONS OF THE WATER METER AND |
| | MAIN SHUT OFF VALVES- SECTION 606.1 FBC P. |
| | |
| | 23) P201: SHOW FULL OPEN SHUT OFF VALVES FOR THE DOWN |
| | FEEDING WATER SUPPLY LINES BY JAN. 118- SECTION |
| | 606.1(5) FBC P. |
| | |
| | 24) P201: THERE APPEARS TO BE A SHUT OFF VALVE MISSING |
| | AT THE RISER BY DOOR 108- SECTION 606.1(4) FBC P. |
| | |
| | 25) P-202, P403, P404 & P502: SHOW SHUTOFF VALVES FOR |
| | THE RISERS UP TO THE HOSE BIBS, BAR AND BATHROOMS- |
| | SECTION 606.1 FBC P. |
| | |
| | 26) P-201, P202, P203, P403, P404, & P502: SHOW THE |
| | LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS, MIXING |
| | VALVES, AND BACKFLOW PREVENTERS- SECTIONS 604.9, 416.4, |
| | 607.1.2, & 608.3 FBC P. PLEASE NOTE THAT BACKFLOW |
| | PREVENTERS ARE REQUIRED FOR WATER SUPPLY LINES TO THE |
| | DISHWASHER, ICE MAKERS, WATER FILTERING SYSTEM, |
| | CHEMICAL STORAGE CABINET, AND BEVERAGE AND COFFEE |
| | DISPENSERS ETC. |
| | |
| | 27) P701: PLEASE LABEL THE LOCATION OF THE CHEMICAL |
| | STORAGE CABINET ON THE DOMESTIC PLANS AND RISER |
| | DRAWINGS- SECTION 608.3 FBC P. CLARIFY IF WASTE WATER |
| | FROM THE CABINET WILL BE DRAINING INTO THE SANITARY |
| | SYSTEM AND PROVIDE A NEUTRALIZING DEVICE IF APPLICABLE- |
| | SECTION 803.1 FBC P. |
| | |
| | 28) P601: PLEASE PROVIDE A PLUMBING DIAGRAM FOR THE |
| | CHEMICAL STORAGE CABINET- SECTION 107.2.1 WPB. |
| | |
| | 29) P701: PROVIDE THE EFFICIENCY RATINGS OF THE WATER |
| | HEATERS IN THE SCHEDULE- TABLE C404.2 FBC EC. |
| | |
| | 30) P701: PROVIDE DRAIN PANS AND DRAIN PAN LINES FOR |
| | THE WATER HEATERS- SECTIONS 504.7.1 & 504.7.2 FBC P. |
| | |
| | 31) P701: PROVIDE A PLUMBING DEVICE SCHEDULE SHOWING |
| | THE MAKES AND MODEL NUMBERS AND LISTINGS OF THE WATER |
| | HAMMER ARRESTORS, BACKFLOW PREVENTERS, MIXING VALVES, |
| | AND TRAP PRIMERS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |