| 2020-12-07 11:14:41 | SUNSET LOUNGE REVISION TO 18110093 |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) 2ND FLOOR BALLROOM EXIT - BALLROOM EXIT SEPARATION |
| | DISTANCE NEEDS TO BE SHOWN (SHOW THE DIAGONAL |
| | MEASUREMENT OF THE BALLROOM AND SHOW THE EXIT DISTANCE |
| | SEPARATION MEASUREMENT) TO COMPLY WITH FBC 1007.1.1 TWO |
| | EXITS OR EXIT ACCESS DOORWAYS. |
| | WHERE TWO EXITS, EXIT ACCESS DOORWAYS, EXIT ACCESS |
| | STAIRWAYS OR RAMPS, OR ANY COMBINATION THEREOF, ARE |
| | REQUIRED FROM ANY PORTION OF THE EXIT ACCESS, THEY |
| | SHALL BE PLACED A DISTANCE APART EQUAL TO NOT LESS THAN |
| | ONE-HALF OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL |
| | DIMENSION OF THE BUILDING OR AREA TO BE SERVED MEASURED |
| | IN A STRAIGHT LINE BETWEEN THEM. (2).WHERE A BUILDING |
| | IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER |
| | SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1 OR |
| | 903.3.1.2, THE SEPARATION DISTANCE SHALL BE NOT LESS |
| | THAN ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL DIMENSION OF THE AREA SERVED. |
| | 2) DOORS THAT PENETRATE FIRE RATED WALLS SHALL BE FIRE |
| | RATED PER FBC 716.5 |
| | 3) 716.5.9 DOOR CLOSING. FIRE DOORS SHALL BE LATCHING |
| | AND SELF- OR AUTOMATIC-CLOSING IN ACCORDANCE WITH THIS |
| | SECTION. |
| | 4) PARKING LOT SHOWS CAR CHARGING STATIONS ADDED - YOU |
| | ARE ADDING AN "ELEMENT" (CHARGING STATION) TO THE |
| | PARKING FACILITY WHICH YOU WILL NEED TO PROVIDE AN |
| | ACCESSIBLE ROUTE, CLEAR FLOOR SPACE AND REACH RANGES TO |
| | COMPLY WITH 2017 FBC ACCESSIBILITY |
| | |
| | |