| 2021-01-19 14:11:22 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110703 |
| | 1/19/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | THE REQUESTED COMMENT RESPONSE NARRATIVE WAS NOT |
| | PROVIDED BY THE ARCHITECT. |
| | |
| | 1) COMMENT #1 FROM THE 1ST REVIEW FAILED- 2ND REQUEST. |
| | SHEET P00.01: PROVIDE PLUMBING FIXTURE CALCULATIONS AND |
| | A SCHEDULE SHOWING THE REQUIRED AND PROVIDED FIXTURES |
| | IN COMPLIANCE WITH TABLE 403.3 FBC P. PLEASE NOTE THAT |
| | DRINKING FOUNTAINS AND A SERVICE SINK ARE REQUIRED |
| | FIXTURES FOR BUSINESS OCCUPANCIES. NO RESPONSE OR |
| | CORRECTED PLANS PROVIDED. PLEASE NOTE THAT A REVISED |
| | P00.01 WAS NOT UPLOADED- SHEET FP00.01 WAS UPLOADED IN |
| | PLACE. |
| | |
| | 2) SHEET P01.02 DOMESTIC WATER PLAN WAS NOT UPLOADED- |
| | CORRECTED SHEET P01.01 WAS UPLOADED IN PLACE. |
| | |
| | 3) NEW PLAN SHEET A801: IT APPEARS IN RESPONSE TO |
| | COMMENT #7 FROM THE 1ST REVIEW, AN ENLARGED RESTROOM |
| | PLAN HAS BEEN PROVIDED, HOWEVER THE PLAN HAS NO ROOM |
| | DIMENSIONS, AND DOES NOT PROVIDE THE DIMENSIONS OF THE |
| | CLEAR FLOOR SPACES FOR THE WATER CLOSET AND LAVATORY- |
| | SECTIONS 604.3 & 606.2 FBC ACC. PLEASE CORRECT THE |
| | PLAN. |
| | |
| | 4) A801: THE RESTROOM DOOR SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION 603.2.3 FBC |
| | ACC. |
| | |
| | 5) NEW PLAN SHEET P01.03: THE 3/8 IN. HW LINE FROM THE |
| | WATER HEATER APPEARS TO BE EXCEEDING THE MAXIMUM 3 FT. |
| | ALLOWABLE PIPING LENGTH PER TABLE C404.5.1 FBC EC. |
| | |
| | 6) COMMENT #7H FROM THE 1ST REVIEW- FAILED. AS NOTED IN |
| | COMMENT #1 DRINKING FOUNTAINS ARE REQUIRED FIXTURES AND |
| | SHALL BE ACCESSIBLE IN ACCORDANCE WITH SECTIONS 211.2 & |
| | 602.1- 602.6 FBC ACC. PROVIDE DRAWINGS AND DETAILS |
| | SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| | FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE DRINKING |
| | FOUNTAIN- SECTION 602.2 FBC ACC. B) KNEE AND TOE |
| | CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS- SECTIONS |
| | 306, 307, & 602.2. C) COMPLIANCE WITH SECTION 307.2 |
| | PROTRUSION LIMITS, THE REQUESTED PLUMBING FIXTURE |
| | CALCULATIONS WERE NOT SUBMITTED AND NEW PLAN SHEET |
| | P00.01 SHOWING THE OVERALL FLOOR PLAN AND LOCATION OF |
| | THE DRINKING FOUNTAIN WAS NOT UPLOADED. |
| | |
| | 7) COMMENT #7J FROM THE 1ST REVIEW- FAILED. SHOW THE |
| | CLEAR FLOOR SPACE APPROACHES TO THE SINKS AND FIXTURES |
| | IN THE CUSTOMER AND COLLEAGUE PANTRIES- SECTION 305 FBC |
| | ACC. FORWARD APPROACH CLEAR FLOOR SPACE DIAGRAMS ARE |
| | SHOWN ON REVISED SHEET A02.01, HOWEVER THE ELEVATION |
| | DETAIL ON A11.03 DOES NOT SHOW THE REQUIRED KNEE AND |
| | TOE CLEARANCES- SECTION 306 FBC ACC. |
| | |
| | 8) COMMENT #8 FROM THE 1ST REVIEW- FAILED. SHEET A00.33 |
| | CODE DATA WAS NOT UPLOADED FOR REVIEW. PLEASE PROVIDE |
| | THE PLAN SHEET- SECTION 107.2.1 WPB. |
| | |
| | 9) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| | 105.1 WPB. PLEASE NOTE THAT THERE IS NO FEE FOR A |
| | SUB-PERMIT THAT IS ISSUED WITH THE PRIMARY PERMIT, |
| | HOWEVER THERE IS A FEE FOR SUB-PERMITS APPLIED FOR |
| | AFTER PRIMARY PERMIT ISSUANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |