Plan Review Notes
Plan Review Notes For Permit 20110703
Permit Number 20110703
Review Stop P
Sequence Number 2
Notes
Date Text
2021-01-19 14:11:222ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20110703
 1/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 THE REQUESTED COMMENT RESPONSE NARRATIVE WAS NOT
 PROVIDED BY THE ARCHITECT.
  
 1) COMMENT #1 FROM THE 1ST REVIEW FAILED- 2ND REQUEST.
 SHEET P00.01: PROVIDE PLUMBING FIXTURE CALCULATIONS AND
 A SCHEDULE SHOWING THE REQUIRED AND PROVIDED FIXTURES
 IN COMPLIANCE WITH TABLE 403.3 FBC P. PLEASE NOTE THAT
 DRINKING FOUNTAINS AND A SERVICE SINK ARE REQUIRED
 FIXTURES FOR BUSINESS OCCUPANCIES. NO RESPONSE OR
 CORRECTED PLANS PROVIDED. PLEASE NOTE THAT A REVISED
 P00.01 WAS NOT UPLOADED- SHEET FP00.01 WAS UPLOADED IN
 PLACE.
  
 2) SHEET P01.02 DOMESTIC WATER PLAN WAS NOT UPLOADED-
 CORRECTED SHEET P01.01 WAS UPLOADED IN PLACE.
  
 3) NEW PLAN SHEET A801: IT APPEARS IN RESPONSE TO
 COMMENT #7 FROM THE 1ST REVIEW, AN ENLARGED RESTROOM
 PLAN HAS BEEN PROVIDED, HOWEVER THE PLAN HAS NO ROOM
 DIMENSIONS, AND DOES NOT PROVIDE THE DIMENSIONS OF THE
 CLEAR FLOOR SPACES FOR THE WATER CLOSET AND LAVATORY-
 SECTIONS 604.3 & 606.2 FBC ACC. PLEASE CORRECT THE
 PLAN.
  
 4) A801: THE RESTROOM DOOR SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION 603.2.3 FBC
 ACC.
  
 5) NEW PLAN SHEET P01.03: THE 3/8 IN. HW LINE FROM THE
 WATER HEATER APPEARS TO BE EXCEEDING THE MAXIMUM 3 FT.
 ALLOWABLE PIPING LENGTH PER TABLE C404.5.1 FBC EC.
  
 6) COMMENT #7H FROM THE 1ST REVIEW- FAILED. AS NOTED IN
 COMMENT #1 DRINKING FOUNTAINS ARE REQUIRED FIXTURES AND
 SHALL BE ACCESSIBLE IN ACCORDANCE WITH SECTIONS 211.2 &
 602.1- 602.6 FBC ACC. PROVIDE DRAWINGS AND DETAILS
 SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE DRINKING
 FOUNTAIN- SECTION 602.2 FBC ACC. B) KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS- SECTIONS
 306, 307, & 602.2. C) COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS, THE REQUESTED PLUMBING FIXTURE
 CALCULATIONS WERE NOT SUBMITTED AND NEW PLAN SHEET
 P00.01 SHOWING THE OVERALL FLOOR PLAN AND LOCATION OF
 THE DRINKING FOUNTAIN WAS NOT UPLOADED.
  
 7) COMMENT #7J FROM THE 1ST REVIEW- FAILED. SHOW THE
 CLEAR FLOOR SPACE APPROACHES TO THE SINKS AND FIXTURES
 IN THE CUSTOMER AND COLLEAGUE PANTRIES- SECTION 305 FBC
 ACC. FORWARD APPROACH CLEAR FLOOR SPACE DIAGRAMS ARE
 SHOWN ON REVISED SHEET A02.01, HOWEVER THE ELEVATION
 DETAIL ON A11.03 DOES NOT SHOW THE REQUIRED KNEE AND
 TOE CLEARANCES- SECTION 306 FBC ACC.
  
 8) COMMENT #8 FROM THE 1ST REVIEW- FAILED. SHEET A00.33
 CODE DATA WAS NOT UPLOADED FOR REVIEW. PLEASE PROVIDE
 THE PLAN SHEET- SECTION 107.2.1 WPB.
  
 9) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB. PLEASE NOTE THAT THERE IS NO FEE FOR A
 SUB-PERMIT THAT IS ISSUED WITH THE PRIMARY PERMIT,
 HOWEVER THERE IS A FEE FOR SUB-PERMITS APPLIED FOR
 AFTER PRIMARY PERMIT ISSUANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  