| 2021-01-18 10:30:54 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20110703 |
| | ADD: 777 S. FLAGLER DR. / 1ST FLOOR/ SUITE??? |
| | CONT: MENEMSHA DEVELOPMENT GROUP |
| | TEL: 781-666-4973 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. JAN. 18TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2 )2ND REQUEST. MISSING INFORMATION. SHEET A00.33 |
| | INDICATES THAT IS WHERE THE CODE REVIEW INFORMATION IS |
| | FOUND BUT THE SAME DOOR SCHEDULE IS FOUND AS ON A0.30. |
| | SHEET A00.33 STILL HAS THE DATE 11/20/2020, NOT |
| | UPDATED. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | |
| | MISSING CODE DATA: |
| | OCCUPANCY GROUP |
| | MINIMUM TYPE OF CONSTRUCTION |
| | FIRE RESISTANCE SEPARATION |
| | LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE |
| | FOLLOWING: |
| | CODE DATA/ BUILDING DATA |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | GROSS OR NET |
| | MEANS OF EGRESS EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | |
| | 3)COMPLIED. |
| | |
| | 4) SEMI-COMPLIED. SHEET A00.30 THE DOOR SCHEDULE DOOR |
| | TYPE C NOW SHOWS THE WIND DESIGN CRITERIA. THE V-ULT |
| | WIND SPEED IS INDICATED AS 160 VULT. PLEASE REFER TO |
| | THE 2017 FBC-BUILDING CODE TABLE FIGURE 1609.3(1) THE |
| | CORRECT WIND SPEED FOR A RISK CATEGORY TYPE II BUILDING |
| | IS 170 VULT OR 132 VASD. THE WIND EXPOSURE IS CORRECT |
| | AS EXPOSURE D. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET A02.01 SHOW A NEW |
| | (REPLACEMENT) EXTERIOR DOOR # 101 AND SIDE LIGHTS. THE |
| | PLANS DO NOT PROVIDE THE WIND DESIGN DATA. 2017 FBC-B |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 4.2. RISK CATEGORY. |
| | |
| | 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 4.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 5-6) COMPLIED. |
| | |
| | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |