Plan Review Notes
Plan Review Notes For Permit 20110703
Permit Number 20110703
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-04 09:15:181ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110703
 12/4/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P00.01: PROVIDE PLUMBING FIXTURE CALCULATIONS
 AND A SCHEDULE SHOWING THE REQUIRED AND PROVIDED
 FIXTURES IN COMPLIANCE WITH TABLE 403.3 FBC P. PLEASE
 NOTE THAT DRINKING FOUNTAINS AND A SERVICE SINK ARE
 REQUIRED FIXTURES FOR BUSINESS OCCUPANCIES.
  
 2) P01.03, SANITARY ISOMETRIC: SHOW A TRAP AT SK-1
 LOCATION. WATER ISOMETRIC: IDENTIFY ALL FIXTURES AND
 SHOW REQUIRED SHUT OFF VALVES AT ALL FIXTURE AND
 APPLIANCE LOCATIONS- SECTION 107.3.5.3 WPB, AND SECTION
 606.2 FBC P.
  
 3) P01.03 WATER ISOMETRIC: SHOW LOCATIONS OF WATER
 HAMMER ARRESTORS, MIXING VALVE AT THE LAVATORY, AND
 BACKFLOW PREVENTERS AT COFFEE MAKER, ICE MAKER
 LOCATIONS- REFER TO SECTIONS 604.9, 416.5, 607.1.2, &
 608.3 FBC P.
  
 4) P02.01: ADD THE MIXING VALVE TO THE LAVATORY
 DETAILS- SECTIONS- 416.5, AND 607.1.2. PLEASE NOTE THAT
 THE POINT OF USE WATER HEATER AT THIS LOCATION SHALL BE
 ASSE 1070 LISTED AND LABELED OR THE MIXING VALVE SHALL
 BE PROVIDED.
  
 5) P02.01: PROVIDE THE EFFICIENCY RATINGS OF THE WATER
 HEATERS IN THE SCHEDULE- TABLE C404.2 FBC EC.
  
 6) P02.01: PLEASE PROVIDE A DEVICE SCHEDULE SHOWING
 MAKES, MODELS AND LISTINGS OF THE WATER HAMMER
 ARRESTORS, MIXING VALVES, AND BACKFLOW PREVENTERS-
 SECTION 107.2.1 WPB.
  
 7) P02.01: ADD A NOTE TO THE SLAB REPAIR DETAIL TO
 INDICATE THE REQUIRED VAPOR BARRIER AND TERMITE
 TREATMENT WILL BE PROVIDED. PLEASE NOTE A COPY OF THE
 TERMITE CERTIFICATE SHALL BE ONSITE FOR FINAL
 INSPECTION APPROVAL- SECTION 107.2.1 WPB.
  
 7) ACCESSIBLE PLUMBING FIXTURE REQUIREMENTS PER FBC
 ACC. THE DRAWINGS AND DETAILS ON SHEETS A02.01 & A11.03
 ARE INCOMPLETE. PLEASE REVISE THE SHEETS TO SHOW:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 WATER CLOSET- SECTION 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
  
 C) TURNING SPACE DIAMETER- SECTION 304.3.
  
 D) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
  
 E) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
  
 F) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
  
 G) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3.
  
 H) AS NOTED IN COMMENT #1 DRINKING FOUNTAINS ARE
 REQUIRED FIXTURES AND SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH SECTIONS 211.2 & 602.1- 602.6 FBC ACC. PROVIDE
 DRAWINGS AND DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR
 FLOOR SPACE FOR A FORWARD APPROACH TO THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 FBC ACC. B)
 KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, SPOUT
 LOCATIONS- SECTIONS 306, 307, & 602.2. C) COMPLIANCE
 WITH SECTION 307.2 PROTRUSION LIMITS.
  
 I) THE PLUMBING PLANS SHOW A WATER COOLER IN THE
 CUSTOMER PANTRY WHICH IS NOT SHOWN ON THE ARCHITECTURAL
 PLANS AND ELEVATION DETAIL. PLEASE CLEARLY SHOW THE
 COOLER ON THE PLANS AND ACCESSIBILITY REQUIREMENTS
 INCLUDING CLEAR FLOOR SPACE APPROACH AND REACH RANGES
 TO CONTROLS- SECTIONS 305 & 308 FBC ACC.
  
 J) SHOW THE CLEAR FLOOR SPACE APPROACHES TO THE SINKS
 AND FIXTURES IN THE CUSTOMER AND COLLEAGUE PANTRIES-
 SECTION 305 FBC ACC.
  
 8) SHEET A00.33 CODE DATA WAS NOT UPLOADED FOR REVIEW.
 PLEASE PROVIDE THE PLAN SHEET- SECTION 107.2.1 WPB.
  
 9) INDICATE THE TYPE OF WALL FINISHES TO BE INSTALLED
 IN THE RESTROOM AND AT THE MOP SINK LOCATION IN
 ACCORDANCE WITH SECTION 310.3 FBC P, AND 1210.2.2 FBC
 B.
  
 10) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER