| 2020-11-30 15:48:33 | PLAN REVIEW / MECHANICAL |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE TIE DOWN DETAIL FOR CU-4. |
| | |
| | PROVIDE ENGINEERING FOR INSTALLATION OF THE CONDENSER |
| | PAD AND MOUNTING OF THE CONDENSER- SECTIONS |
| | M1305.1.4.1, M1307.2 AND M1401.4 FBC RES. |
| | |
| | M1401.4EXTERIOR INSTALLATIONS. |
| | EQUIPMENT AND APPLIANCES INSTALLED OUTDOORS SHALL BE |
| | LISTED AND LABELED FOR OUTDOOR INSTALLATION. SUPPORTS |
| | AND FOUNDATIONS SHALL PREVENT EXCESSIVE VIBRATION, |
| | SETTLEMENT OR MOVEMENT OF THE EQUIPMENT. SUPPORTS AND |
| | FOUNDATIONS SHALL BE IN ACCORDANCE WITH SECTION |
| | M1305.1.4.1. |
| | |
| | 2. PROVIDE SERVICE OUTLET FOR CU-4. |
| | |
| | E3901.12 HVAC OUTLET. |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM) |
| | OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED |
| | TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING |
| | MEANS. (210.63) |
| | |
| | 3. PROVIDE DETAIL FOR AH-4 CONDENSATE DISPOSAL. |
| | |
| | M1411.3 CONDENSATE DISPOSAL. |
| | CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE |
| | CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE |
| | OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM |
| | HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT |
| | LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| | (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO |
| | A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A |
| | NUISANCE. |
| | |
| | 4. PROVIDE DETAIL FOR BATHROOM EXHAUST FANS. |
| | |
| | M1501.1OUTDOOR DISCHARGE. |
| | THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM |
| | SHALL BE DISCHARGED TO THE OUTDOORS IN ACCORDANCE WITH |
| | SECTION M1506.3. AIR SHALL NOT BE EXHAUSTED INTO AN |
| | ATTIC, SOFFIT, RIDGE VENT OR CRAWL SPACE. |
| | |
| | 5. PROVIDE LOCKING FREON PORTS. |
| | |
| | M1411.8 LOCKING ACCESS PORT CAPS. |
| | REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL |
| | BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR |
| | SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED |
| | ACCESS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |