| 2020-12-10 12:51:11 | ADDITION AND REMODEL GUEST HOUSE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY |
| | THEDESIGNER. |
| | 2) PLEASE SHOW THE CEILING HEIGHT TO COMPLY WITH FBC |
| | R305.1 |
| | 3) PLEASE SHOW THE REQUIRED EXTERIOR WATER BARRIER - |
| | FBC R703.2 WATER-RESISTIVE BARRIER. ONE LAYER OF NO. 15 |
| | ASPHALT FELT, FREE FROM HOLES AND BREAKS, COMPLYING |
| | WITH ASTM D226 FOR TYPE 1 FELT OR OTHER APPROVED |
| | WATER-RESISTIVE BARRIER SHALL BE APPLIED OVER STUDS OR |
| | SHEATHING OF ALL EXTERIOR WALLS. |
| | 4) PLEASE SHOW THE WALL AND CEILING INSULATION TYPE AND |
| | "R" VALUE ON THE DRAWINGS. |
| | 5) PLEASE SHOW THE VENTILATION TYPE AND LOCATION FOR |
| | THE ROOF RAFTERS - FBC R806.1VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN OR SNOW. |
| | 6) PLEASE PROVIDE THE STRUCTURAL DETAILS SHOWING ALL |
| | ATTACHMENTS FOR THE ADDED ROOFING OUTLOOKERS SHOWN ON |
| | DRAWING A501. |
| | 7) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE OVERHEAD DOORS. |
| | 8) YOU UPLOADED A STOREFRONT PRODUCT APPROVAL TO THE |
| | SUPORTING DOC. FOLDER - PLEASE SHOW THE LOCATION FOR |
| | THE STOREFRONT GLASS SYSTEM ON THE FLOOR PLAN. |
| | 9) THE BUILDING DEMO NEEDS TO BE ON A SEPARATE PERMIT - |
| | PLEASE PROVIDE THE DEMO PERMIT NUMBER. |