Plan Review Notes
Plan Review Notes For Permit 20110673
Permit Number 20110673
Review Stop M
Sequence Number 1
Notes
Date Text
2020-11-19 15:30:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110673
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. SEE PERMIT # 20100803 FOR
 PLANS
  
 1) PLEASE PROVIDE A COMCHECK FOR EACH TENANT SPACE. IT
 SHOULD INCLUDE ONLY THE RTU?S FOR THAT PARTICULAR
 TENANT SPACE. FBC 107.2
  
 2) SHEET M-1- DRAWING INDICATES RTU-2 AND RTU-3 IN BAY
 2 (ADDRESS 7032-7034), THE ROOFTOP PACKAGE AIR
 CONDITIONING SCHEDULE DOES NOT INCLUDE RTU-3. PLEASE
 PROVIDE RTU-3 SCHEDULE DETAILS. FBC 107.2
  
 3) SHEET M-1: PLEASE USE THE OCCUPANT COUNT LOCATED ON
 SHEET A-0.1 FOR THE MERCANTILE OCCUPANCY FOR UNITS
 (ADDRESS 7032-7034) FBC 107.2
  
 4) SHEET M-1: THE FAN SCHEDULE INDICATES EF_1,2 ARE 525
 CFM, EF-1 ON THE DRAWING FOR TENANT ADDRESS (ADDRESS
 7032-7034) INDICATES THE FAN IS 90 CFM. PLEASE MAKE THE
 FAN SCHEDULE CONSISTENT. FBC 107.2
  
 5) SHEET M-1: THE FAN SCHEDULE INDICATES THE BATH
 EXHAUST FANS ARE ROOF MOUNTED BUT THE DRAWING INDICATES
 THAT BOTH EXHAUST FANS ARE MOUNTED AT CEILING AND
 DUCTED TO ROOF TERMINATIONS. PLEASE BE CONSISTENT. FBC
 107.2
  
 6) SHEET M-1: BAY 1 (ADDRESS 7036) OCCUPANCY IS
 BUSINESS PER SHEET A-1. PLEASE PROVIDE THE CORRECT
 OCCUPANCY (BUSINESS) IN THE OUTSIDE AIR CALCULATIONS ON
 SHEET M-1. FBC 107.2
  
 7) SHEET M-1: BAY 1 (ADDRESS 7036) THE FAN SCHEDULE
 INDICATES EF_1,2 ARE 525 CFM, EF-2 ON THE DRAWING FOR
 TENANT (ADDRESS 7036) INDICATES THE FAN IS 90 CFM.
 PLEASE MAKE THE FAN SCHEDULE CONSISTENT. FBC 107.2
 8) IS THE TENANT SPACE (ADDRESS-7036) GOING TO HAVE ANY
 DUCTWORK INSTALLED?
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  