| 2020-12-01 12:23:34 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100465 |
| | 12/1/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ACCORDING TO THE SUBMITTED SURVEY AND FLOOD MAPS THE |
| | PROPOSED LOCATION OF 500-GALLON LP TANK APPEARS TO BE |
| | LOCATED IN AN AE FLOOD ZONE. PLEASE PROVIDE COMPLETE |
| | ENGINEERING FOR ANCHORING THE TANK TO PREVENT |
| | FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION |
| | 6.6.1.6. NFPA 58, AND SECTION R322.2.4 FBC RES. PLEASE |
| | INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE |
| | BURIAL DEPTH, ANCHORING BASE MATERIAL, AND THE TYPES, |
| | SIZES, AND NUMBERS OF ANCHORS, CABLES OR STRAPS, AND |
| | THE TYPE OF PROTECTIVE SLEEVES FOR THE CABLES OR |
| | STRAPS. |
| | |
| | 2) CORRECT THE NOTE ON SURVEY TO SHOW THE REQUIRED 10 |
| | FT. CLEARANCE FOR THE GENERATOR EXHAUST TO THE WINDOW |
| | AND DOORS OPENINGS- SECTION R303.5 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |