| Plan Review Notes For Permit 20110624 |
| Permit Number |
20110624 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-11-23 14:13:06 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | 2ND BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, PLEASE PROVIDE ENGINEER'S SIGNED/SEALED | | | CALCULATIONS FOR UPLIFT PRESSURES AND FASTENER SPACING | | | AT ROOF ZONES 2 AND 3. | | | (THE PRODUCT APPROVAL LIMITATION #9 DOES NOT APPLY AS | | | THE SELECTED SYSTEM'S UPLIFT PRESSURE CAPACITY DOES NOT | | | MEET THE REQUIRED UPLIFT PRESSURES. THEREFORE, PRODUCT | | | APPROVAL LIMITATION # 7 APPLIES). |
|