| Plan Review Notes For Permit 20110596 |
| Permit Number |
20110596 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-17 10:00:51 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 | | | [email protected] | | | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R6 ROOF SYSTEM NO. W-5; ZONE 2 & 3; | | | PERIMETER & CORNER AREA BASE SHEET ATTACHMENT: PLEASE | | | SELECT; EXPOSURE; ENCLOSURE; ROOF HEIGHT; ZONE AND | | | ULTIMATE WIND SPEED. ALL APPLICABLE DETAILS AND | | | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT | | | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT | | | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED | | | SITE-SPECIFIC ENGINEERING | | | |
|