| Date |
Text |
| 2022-04-05 15:15:06 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20110536 |
| | ADD: 106 N. OLIVE AVE. |
| | CONT: TRIBECA INVESTMENTS INC |
| | TEL: 561-239-0750 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: TUES. APRIL 05TH/ 2022 |
| | ACTION: DENIED |
| | |
| | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B). WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1A)3RD REQUEST. THE REVISED PLANS SP-01INDICATE THEY |
| | WERE DRAWN TO THE 2020 FBC-BUILDING. PLEASE BE AWARE |
| | THIS PLAN WAS SUBMITTED ON 11/12/2020 UNDER THE 2017 |
| | FBC-BUILDING. THE 7TH EDITION 2020 FBC FAMILY OF CODES |
| | WAS ADOPTED DEC. 31ST/ 2020 PLANS SUBMITTED ON THIS |
| | DATE OR AFTER THIS DATE WOULD BE UNDER THE 7TH EDITION |
| | 2020 FBC. |
| | |
| | 1B) 4TH REQUEST. PROVIDE A SURVEY AND SHOW ON THE |
| | SURVEY WHERE THIS CONSTRUCTION WILL OCCUR. 7.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA. THE LOCATION OF THE |
| | PROPERTY LINE MUST BE DETERMINED FOR THE 2017 FBC- |
| | BUILDING CODE FOR COMPLIANCE WITH 3202.2 & 3202.3 & |
| | 3202.3.1. AS WELL AS THE ZONING REQUIREMENTS SEE ZONING |
| | COMMENTS. |
| | |
| | 2) 4TH REQUEST/ SEE BUILD. TYPE NOT LISTED. UNDER THE |
| | HEADING SCOPE OF WORK THE PLAN SP-01 DOES NOT INDICATE |
| | TO THE CONSTRUCTION TYPE THIS BUILDING IS. PLEASE NOTE |
| | THE BUILDING CONSIST OF MANY ADDRESSES. THE FURTHEST |
| | EAST PORTION OF THE BUILDING IS A 4-STORY BUILDING 1ST |
| | & 2ND FLOOR A-3 OCCUPANCY AND THE 3RD & 4TH FLOOR |
| | BUSINESS OCCUPANCY, THE BUILDING IS FULLY FIRE |
| | SPRINKLERED. PLEASE PROVIDE THE MINIMUM BUILDING TYPE. |
| | SHOW COMPLIANCE WITH THE 2017 FBC-B TABLE 504.4 |
| | (CONSTRUCTION TYPE III-B/ FULLY SPRINKLERED), & SECTION |
| | 1406 COMBUSTIBLE MATERIALS ON THE EXTERIOR SIDE OF |
| | EXTERIOR WALLS .1406.2.1(3) FIRE RETARDANT TREATED WOOD |
| | COMPLYING WITH SECTON 2303.2. |
| | |
| | 3) 4TH REQUEST. THE ISSUE IS THE ASCE &-16 IS FOR PLANS |
| | DESIGNED UNDER THE 2020 FBC-B, THIS PLAN CAME IN ON |
| | 11/12/2020 UNDER THE 2017 FBC & ASCE 7-10. SHOW ROOF |
| | PRESSURES FOR ROOF ZONES 1, 2, 3, 2017 FBC-B 1603.1.4 |
| | WIND DESIGN DATA. PROVIDE WIND ZONE PRESSURES FOR |
| | COMPONENTS AND CLADDING AFFECTIVE WIND AREA 10 SQ. FT. |
| | |
| | 4) 3RD REQUEST. SHEET S-1 STATES THE USE OF FL |
| | 11560.1-R3, PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B |
| | SECTIONS: |
| | |
| | 4A) 4TH REVIEW/ SEMI-COMPLIED THIS REVIEW NO STRAP OR |
| | HANGER PRODUCT APPROVALS WERE SUBMITTED. . COMPONENTS & |
| | CLADDING. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(C) 4TH REQUEST. PANEL WALLS: STRAPS & HANGERS, |
| | BUCKETS |
| | |
| | 4B) 4TH REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 4C-D) COMPLIED. |
| | |
| | 5) 12 PAGES OF STRUCTURAL CALCULATIONS. ARE DESIGNED TO |
| | THE 2020 FBC-BUILDING CODE. . PLEASE BE AWARE THIS PLAN |
| | WAS SUBMITTED ON 11/12/2020 UNDER THE 2017 |
| | FBC-BUILDING. THE 7TH EDITION 2020 FBC FAMILY OF CODES |
| | WAS ADOPTED DEC. 31ST/ 2020 PLANS SUBMITTED ON THIS |
| | DATE OR AFTER THIS DATE WOULD BE UNDER THE 7TH EDITION |
| | 2020 FBC. |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |