| 2021-06-04 11:58:42 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20110536 |
| | ADD: 106 N. OLIVE AVE. |
| | CONT: TRIBECA INVESTMENTS INC |
| | TEL: 561-239-0750 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. MARCH 15TH/ 2021 |
| | ACTION: DENIED |
| | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B). WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1A)NEW COMMENT. THE REVISED PLANS INDICATE THEY WERE |
| | DRAWN TO THE 2020 FBC-BUILDING. PLEASE BE AWARE THIS |
| | PLAN WAS SUBMITTED ON 11/12/2020 UNDER THE 2017 |
| | FBC-BUILDING. THE 7TH EDITION 2020 FBC FAMILY OF CODES |
| | WAS ADOPTED DEC. 31ST/ 2020 PLANS SUBMITTED ON THIS |
| | DATE OR AFTER THIS DATE WOULD BE UNDER THE 7TH EDITION |
| | 2020 FBC. |
| | |
| | 1B 3RD REQUEST. PROVIDE A SURVEY AND SHOW ON THE SURVEY |
| | WHERE THIS CONSTRUCTION WILL OCCUR. 107.3.5 MINIMUM |
| | PLAN REVIEW CRITERIA. THE LOCATION OF THE PROPERTY LINE |
| | MUST BE DETERMINED FOR THE 2017 FBC- BUILDING CODE FOR |
| | COMPLIANCE WITH 3202.2 & 3202.3 & 3202.3.1. AS WELL AS |
| | THE ZONING REQUIREMENTS SEE ZONING COMMENTS. |
| | |
| | 2) 3RD REQUEST/ SEE BUILD. TYPE LISTED> . UNDER THE |
| | HEADING SCOPE OF WORK THE PLAN S-1 DOES NOT INDICATE TO |
| | THE CONSTRUCTION TYPE THIS BUILDING IS. PLEASE NOTE THE |
| | BUILDING CONSIST OF MANY ADDRESSES. THE FURTHEST EAST |
| | PORTION OF THE BUILDING IS A 4-STORY BUILDING 1ST & 2ND |
| | FLOOR A-3 OCCUPANCY AND THE 3RD & 4TH FLOOR BUSINESS |
| | OCCUPANCY, THE BUILDING IS FULLY FIRE SPRINKLERED. |
| | PLEASE PROVIDE THE MINIMUM BUILDING TYPE. SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B TABLE 504.4 |
| | (CONSTRUCTION TYPE III-B/ FULLY SPRINKLERED) , & |
| | SECTION 1406 COMBUSTIBLE MATERIALS ON THE EXTERIOR SIDE |
| | OF EXTERIOR WALLS . |
| | |
| | 3) 2ND REQUEST. PRESSURES SHOWN ARE FOR WINDOWS, DOORS |
| | AND GARAGE DOORS NOT FOR ROOF PRESSURES. THE @ND ISSUE |
| | IS THE ASCE &-16 IS FOR PLANS DESIGNED UNDER THE 2020 |
| | FBC-B, THIS PLAN CAME IN ON 11/12/2020 UNDER THE 2017 |
| | FBC & ASCE 7-10. SHOW ROOF PRESSURES FOR ROOF ZONES 1, |
| | 2, 3, 2017 FBC-B 1603.1.4 WIND DESIGN DATA. PROVIDE |
| | WIND ZONE PRESSURES FOR COMPONENTS AND CLADDING |
| | AFFECTIVE WIND AREA 10 SQ. FT. |
| | |
| | 4) 2ND REQUEST. SHEET S-1 STATES THE USE OF FL |
| | 11560.1-R3PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B |
| | SECTIONS: |
| | |
| | 4A) 3RD REQUEST/ SEMI-COMPLIED THIS REVIEW NO STRAP OR |
| | HANGER PRODUCT APPROVALS WERE SUBMITTED. . COMPONENTS & |
| | CLADDING. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(C) 2ND REQUEST. PANEL WALLS: STRAPS & HANGERS, |
| | BUCKETS |
| | (31)(D) 2ND REQUEST. ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 4B) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 4C) NEW COMMENT. THE EAST PORTION OF THE BUILDING IS |
| | TERRA COTTA, THE ADDITIONS TO THE WEST ( 2 STORY |
| | PORTION) IT IS UNKNOWN IF THIS IS TERRA COTTA OR CBC |
| | CONSTRUCTION. VERIFICATION OF THE WALL MATERIAL NEEDS |
| | TO BE ADDRESSES SINCE THE ANCHORS ARE ? INCH X 6 INCH |
| | GALV. TAPCONS. @ 6 INCHES ON CENTER. |
| | |
| | 4D) 2ND REQUEST. 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED |
| | BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL IDENTIFY, |
| | ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| | SYSTEM, MATERIALS, VENTING, FASTENING REQUIREMENTS, |
| | FLASHING REQUIREMENTS AND WIND RESISTANCE RATING THAT |
| | ARE REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| | INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND |
| | CRITERIA REQUIRED FOR THE SPECIFIC SITE. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |