| Plan Review Notes For Permit 20110530 |
| Permit Number |
20110530 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-03-18 13:14:29 | STOREFRONT WINDOWS AND DOORS | | | AND GUARD RAILS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 4TH REVIEW | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE ANCHOR TYPE AND SIZE FOR THE | | | INTERIOR SOFFIT FRAMING TO THE EXISTING STRUCTURE - ON | | | DRAWING A-2 (REFLECTED CEILING PLAN) | | | 2) DRAWINGS (S-1) AND (S-2) NEED TO BE SIGNED AND | | | SEALED BY THE ENGINEER. | | | 3) PROVIDED STOREFRONT SHOP DRAWINGS FROM THOMAS J. | | | TWOMEY P.E. NEED TO BE REVIEWED AND MARKED APPROVED BY | | | THE ARCHITECT OF RECORD (DAVID MILLER) | | | 4) GLASS RAILING DETAILS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE ARCHITECT OF RECORD (DAVID MILLER). | | | | | | |
|