| 2021-02-23 09:20:20 | STOREFRONT WINDOWS AND DOORS |
| | ROOFING, GUARD RAILS |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | 3RD REVIEW |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | |
| | 1) BUILDING PERMIT APPLICATION SHOWS "WORK DESCRIPTION" |
| | AS "REPLACING STOREFRONTS" - THE PLANS PROVIDED FOR |
| | THIS PERMIT NUMBER SHOW STOREFRONTS, ROOFING, GUARD |
| | RAILINGS, INTERIOR SOFFITS ETC. PLEASE CLARIFY THE |
| | BUILDING PERMIT APPLICATION AND REMOVE DRAWINGS THAT DO |
| | NOT PERTAIN TO THIS PERMIT. |
| | 2) PLEASE SHOW THE ANCHOR TYPE AND SIZE FOR THE |
| | INTERIOR SOFFIT FRAMING TO THE EXISTING STRUCTURE - ON |
| | DRAWING A-2 |
| | 3) THERE ARE MULTIPLE DRAWINGS OF (CS-1) (A-1) (A-2) |
| | (A-3) IN PROJECTDOX. |
| | 4) DRAWINGS (S-1) AND (S-2) NEED TO BE SIGNED AND |
| | SEALED BY THE ENGINEER. |
| | 5) PLEASE SHOW THAT DOOR THRESHOLDS, DOOR WIDTHS, DOOR |
| | OPENING AND CLOSING - COMPLY WITH ACCESSIBILITY |
| | REQUIREMENTS FBC ACCESSIBILITY 404 |
| | 6) PROVIDED STOREFRONT SHOP DRAWINGS FROM THOMAS J. |
| | TWOMEY P.E. NEED TO BE SIGNED AND SEALED. |
| | 7) ROOF PRODUCT APPROVAL PROVIDED (SIKA CORPORATION |
| | 14-1020.08) HAS EXPIRED - PLEASE PROVIDE AN UP DATED |
| | PRODUCT APPROVAL. |
| | 8) ROOF PRODUCT APPROVAL PROVIDED (SIKA CORPORATION |
| | 14-1020.08) IS FOR ATTACHMENT TO A CONCRETE ROOF DECK |
| | (DOES NOT INCLUDE INSULATION AS SHOWN ON DRAWING A-1) |
| | 9) PLEASE PROVIDE THE GLASS RAILING DETAILS - SHOW THE |
| | GLASS TO COMPLY WITH FBC 2407.1MATERIALS. |
| | GLASS USED IN A HANDRAIL, GUARDRAIL OR GUARD SECTION |
| | SHALL BE LAMINATED GLASS CONSTRUCTED OF FULLY TEMPERED |
| | OR HEAT-STRENGTHENED GLASS AND SHALL COMPLY WITH |
| | CATEGORY II OR CPSC 16 CFR PART 1201 OR CLASS A OF ANSI |
| | Z97.1. GLAZING IN RAILING IN-FILL PANELS SHALL BE OF AN |
| | APPROVED SAFETY GLAZING MATERIAL THAT CONFORMS TO THE |
| | PROVISIONS OF SECTION 2406.1.1. FOR ALL GLAZING TYPES, |
| | THE MINIMUM NOMINAL THICKNESS SHALL BE 1/4 INCH (6.4 |
| | MM). |
| | 10) A SEPARATE PERMIT APPLICATION (MARKED ROOFING) WILL |
| | BE REQUIRED FOR THE ROOFING. |