| 2021-01-14 15:36:35 | STOREFRONT WINDOWS AND DOORS |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | 2ND REVIEW |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | THESE COMMENTS ARE ONLY FOR THE REPLACEMENT OF THE |
| | STOREFRONT PER THE BUILDING PERMIT APPLICATION |
| | PROVIDED. |
| | 1) BUILDING PERMIT APPLICATION SHOWS "WORK DESCRIPTION" |
| | AS "REPLACING STOREFRONTS" - THE PLANS PROVIDED FOR |
| | THIS PERMIT NUMBER SHOW STOREFRONTS, ROOFING, GUARD |
| | RAILINGS, INTERIOR SOFFITS ETC. PLEASE CLARIFY THE |
| | BUILDING PERMIT APPLICATION AND REMOVE DRAWINGS THAT DO |
| | NOT PERTAIN TO THIS PERMIT. |
| | 2) PLEASE SHOW THE ANCHOR TYPE AND SIZE FOR THE |
| | INTERIOR SOFFIT FRAMING TO THE EXISTING STRUCTURE - ON |
| | DRAWING A-2 |
| | 3) THERE ARE MULTIPLE DRAWINGS OF (CS-1) (A-1) (A-2) |
| | (A-3) IN PROJECTDOX. |
| | 4) DRAWINGS (S-1) AND (S-2) NEED TO BE SIGNED AND |
| | SEALED BY THE ENGINEER. |
| | 5) PLEASE SHOW THAT DOOR THRESHOLDS, DOOR WIDTHS, DOOR |
| | OPENING AND CLOSING - COMPLY WITH ACCESSIBILITY |
| | REQUIREMENTS FBC ACCESSIBILITY 404 |
| | 6) PROVIDED STOREFRONT SHOP DRAWINGS FROM THOMAS J. |
| | TWOMEY P.E. NEED TO BE SIGNED AND SEALED. |
| | 7) ALL SHOP DRAWINGS AND PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE PROJECT DESIGNER OF |
| | RECORD OR BE LISTED ON THE CONSTRUCTION DRAWINGS. |
| | 8) PRODUCT APPROVALS PROVIDED ARE NOT THE PRODUCT |
| | APPROVALS LISTED ON THE PROVIDED SHOP DRAWINGS. PLEASE |
| | REVISE THE SHOP DRAWINGS TO SHOW THE PRODUCT APPROVALS |
| | ADDED TO PLAN REVIEW OR PROVIDE THE PRODUCT APPROVALS |
| | LISTED ON THE SHOP DRAWINGS. |
| | |
| | |