| 2020-11-25 14:50:48 | STOREFRONT WINDOWS AND DOORS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | THESE COMMENTS ARE ONLY FOR THE REPLACEMENT OF THE | | | STOREFRONT PER THE BUILDING PERMIT APPLICATION | | | PROVIDED. | | | 1) BUILDING PERMIT APPLICATION SHOWS "WORK DESCRIPTION" | | | AS "REPLACING STOREFRONTS" - THE PLANS PROVIDED FOR | | | THIS PERMIT NUMBER SHOW STOREFRONTS, ROOFING, GUARD | | | RAILINGS, INTERIOR SOFFITS ETC. PLEASE CLARIFY THE | | | BUILDING PERMIT APPLICATION AND REMOVE DRAWINGS THAT DO | | | NOT PERTAIN TO THIS PERMIT. | | | 2) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE STOREFRONT WINDOWS AND DOORS. | | | (COMPLETE = FRONT PAGES AND THE INSTALLATION | | | INSTRUCTIONS) | | | 3) PLEASE SHOW THE ANCHOR TYPE AND SIZE FOR THE | | | INTERIOR SOFFIT FRAMING TO THE EXISTING STRUCTURE - ON | | | DRAWING A-2 | | | 4) THERE ARE MULTIPLE DRAWINGS OF (CS-1) (A-1) (A-2) | | | (A-3) IN PROJECTDOX. | | | 5) DRAWINGS (S-1) AND (S-2) NEED TO BE SIGNED AND | | | SEALED BY THE ENGINEER. | | | 6) PLEASE SHOW THAT DOOR THRESHOLDS, WIDTHS, OPENING | | | AND CLOSING - COMPLY WITH ACCESSIBILITY REQUIREMENTS | | | FBC ACCESSIBILITY 404 | | | | | | |
|