2020-12-17 07:54:0312/17/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1.A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW BY A
 LICENSED CONTRACTOR. IT WILL BE REQUIRED AT THE WATER
 METER DUE TO CONSTRUCTION AND IT WILL NEED TO BE
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT PER THEIR CROSS CONNECTION PROGRAM,.
  
 2. A PERMIT IS REQUIRED BY A LICENSED CONTRACTOR AND
 MUST BE CERTIFIED BY UTILITIES BEFORE FINAL
 INSPECTION.THESE ARE THE ITEMS THAT WILL BE NEEDED ON
 THE APPLICATION REVIEW FOR THE BACKFLOW;
  
 A. ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE
 (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED
 ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN
 ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL
 NOT BE APPROVED.
  
 B. OPTIONAL, A SITE PLAN DEPICTING THE GENERAL LOCATION
 OF THE PROPOSED BACKFLOW PREVENTION DEVICE, THIS CAN BE
 DONE BY GOING TO THE PROPERTY APPRAISER WEBSITE AND
 PRINT OUT A STRUCTURAL LAYOUT OF THE BUILDING AND HAND
 DRAW THE METER LOCATION WITH THE BACKFLOW.
  
 C. A COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF THE
 WORK SECTION ON THE PERMIT APPLICATION.
  
 PLEASE TRY HAVE THE PERMIT ISSUED BEFORE SECOND REVIEW
 TO VERIFY COMPLIANCE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  