| 2020-12-02 15:41:15 | FAILED |
| | |
| | PLEASE CLARIFY WHERE THE WORK IS BEING DONE. THE PERMIT |
| | AND THE PLANS LIST DIFFERENT ADDRESSES AND THE GROUND |
| | AND SECOND FLOOR KEY PLANS HIGHLIGHT TWO LOCATIONS THAT |
| | DO NOT CONNECT. ADDITIONALLY, THE TWO SECOND FLOOR |
| | BAYS, WHILE ADJACENT, DO NOT INTERNALLY CONNECT. IT |
| | SEEMS THAT SEPARATE PERMITS FOR EACH LOCATION WILL BE |
| | REQUIRED. |
| | |
| | THE PLANS FOR THE SECOND FLOOR WORK DO NOT MATCH THE |
| | LOCATION OF THE WORK ON THE SECOND FLOOR KEY PLAN. THE |
| | KEY, MECHANICAL, ELECTRICAL AND FIRE PROTECTION PLANS |
| | SHOW A SIGNIFICANTLY SMALLER AREA AND HAS NO STOREFRONT |
| | WHEN COMPARED TO THE DEMOLITION, ARCHITECTURAL AND LIFE |
| | SAFETY PLANS. ALL PLANS MUST SHOW THE SAME ACCURATE |
| | CONDITIONS. |
| | |
| | PLEASE PROVIDE A DESCRIPTION OF WHAT IS INTENDED TO |
| | OCCUR IN EACH OF THE SPACES. |
| | |
| | ELECTRICAL NOTE #2 (PROVIDED 4 TIMES) CALLS OUT A |
| | WEATHERPROOF J-BOX AND 3/4 INCH CONDUIT WITH PULLWIRE |
| | STUBBED INTO ACCESSIBLE TENANTS CEILING ARE FOR |
| | EXTERIOR SIGNAGE. PROVIDE A DETAIL FOR EACH DIFFERENT |
| | LOCATION SO THAT STAFF CAN VERIFY THAT THIS ELECTRICAL |
| | CONNECTION COMPLIES WITH THE ROSEMARY SQUARE TENANT |
| | SIGN CRITERIA REQUIREMENT THAT ALL LIGHTING CONDUIT, |
| | WIRING, BALLAST BOXES, TRANSFORMERS, AND OTHER |
| | EQUIPMENT NECESSARY FOR SIGN CONNECTION SHALL BE |
| | CONCEALED AND NOT VISIBLE TO THE PUBLIC. |
| | |