| 2020-12-16 17:17:33 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110522 |
| | 12/16/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P101: PLEASE PROVIDE A SLAB REPAIR DETAIL FOR |
| | SLABS REMOVED TO INSTALL DRAIN AND VENT PIPING- SECTION |
| | 107.2.1 WPB. |
| | |
| | 2) P101: PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR |
| | INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW |
| | PREVENTER- SECTION 105.1 AND 107.2.1 WPB. A FL. |
| | LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE |
| | PERMIT FOR INSTALLATION OF THE BACKFLOW PREVENTER IN |
| | ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB |
| | CODE OF ORDINANCES. THE DEVICE SHALL BE TESTED AND |
| | CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO |
| | FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE |
| | CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT |
| | 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |