| 2021-03-01 11:14:51 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. A NEW AFFIDAVIT WAS SUBMITTED, BUT DOES NOT REFER TO | | | THE VERSION NUMBER FOR EACH PAGE AND DOES NOT REFER TO | | | SHOP DRAWINGS, PRODUCT APPROVALS, ETC. (SEE PREVIOUS | | | PRIVATE PROVIDER REVIEW). THE AFFIDAVIT ONLY LISTS PLAN | | | PAGES AND SURVEY. AFFIDAVIT REFERS TO 16 PAGES, BU | | | TTHERE ARE 17 PAGES IN THE PROJECTDOX UPLOAD AS WELL AS | | | MANY SUPPORTING DOCUMENTS. SOME PLANS WERE SUBMITTED | | | THREE TIMES; NOT CLEAR WHICH OF THE VERSIONS WERE | | | REVIEWED BY THE PRIVATE PROVIDER AS WE DID NOT GET A | | | NEW AFFIDAVIT WITH VERSION NUMBERS FOR EACH REVIEW. | | | | | | FOR EXAMPLE: | | | COVER SHEET A1 (WHICH INCLUDES WIND DESIGN CRITERIA, | | | GENERAL NOTES, ETC.) IS DIGITALLY SIGNED 12/14/20. THIS | | | WAS 2ND VERSION, NO SHOP DRAWING REVIEW BY UNIVERSAL | | | ENGINEERING. | | | SHEET A3 INCLUDES A SHOP DRAWING REVIEW, DIGITALLY | | | SIGNED 11/8. | | | SHEET E1 IS NOT DIGITALLY SIGNED, IS VERSION 3 DATED | | | 1/9/21, NO SHOP DRAWING REVIEW BY UNIVERSAL. | | | | | | IF AN AFFIDAVIT WAS PROVIDED EVERY CYCLE, OR SHOP | | | DRAWING REVIEW WAS DONE EVERY CYCLE, THE VERSION | | | REVIEWED WOULD BE CLEARER (BUT WOULD BE 100% CLEAR WITH | | | EITHER A SHOP DRAWING REVIEW OR AN AFFIDAVIT REFERRING | | | TO VERSION DATE). AS SUBMITED, I CANNOT DETERMINE WHICH | | | SUBMITTALS WERE REVIEWED BY THE PRIVATE PROVIDER. | | | REVIEW OF SUPPORTING DOCUMENTS DOES NOT APPEAR TO HAVE | | | BEEN DONE. | | | | | | | | | | | | | | | | | | |
|