Plan Review Notes
Plan Review Notes For Permit 20110521
Permit Number 20110521
Review Stop B
Sequence Number 3
Notes
Date Text
2021-01-28 10:30:47NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES P1 P2 AND P3 WHICH REQUIRE A HIGHER
 PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL
 (-52.5) - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE
 PRODUCT APPROVAL. DRAWINGS DO NOT SHOW THE REQUIRED
 ROOF COMPONENT PRESSURES - REQUIRED PRESSURES FROM FBC
 TABLE R301.2(2) P1=(-64.11) P2=(-84.62) P3=(-115.33)
 2) GUARD RAIL "VIEW RAIL" DRAWINGS CANNOT BE ACCEPTED
 AS SIGNED AND SEALED UNLESS SIGNED AND SEALED FROM A
 FLORIDA LICENSED ARCHITECT OR ENGINEER.FBC WPB 107.1
 (ALSO, ALL SHOP DRAWINGS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD)
 3) GUARD RAILS ARE SUBJECT TO LIVE LOADS - PLEASE
 PROVIDE AN APPROVED PRODUCT APPROVAL - OR - PROVIDE
 GUARD RAIL ATTACHMENT DETAILS ALONG WITH THE STRUCTURAL
 CALCULATIONS THAT SHOW COMPLIANCE WITH THE REQUIRED
 LIVE LOADS PER FBC TABLE R301.5 (WHICH MUST BE SIGNED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN) - OR- SIGNED
 AND SEALED GUARDRAIL ATTACHMENT DETAILS FROM A FLORIDA
 LICENSED ARCHITECT OR ENGINEER.
 4) DEMO PERMIT IS (20110526)
 5) ROOF PERMIT, GUARD RAIL SHOP DRAWINGS AND ALL
 PRODUCT APPROVALS (WINDOWS, DOORS, ROOFING ETC.) CAN BE
 DEFERRED SUBMITTALS IF THEY ARE LISTED TO BE DEFERRED
 SUBMITTALS ON THE CONSTRUCTION DOCUMENTS SEE- FBC
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY
 SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE
 BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED
 AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF
 THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
  