| Plan Review Notes For Permit 20110521 |
| Permit Number |
20110521 |
|
| Review Stop |
PRIVATEPRV |
| Sequence Number |
10 |
|
| Notes |
| Date |
Text |
| 2021-05-12 18:07:48 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FS553.791, THE AFFIDAVIT FOR SHEET P2 IS FOR VERSION | | | 2. THE PLAN UPLOADED IS FOR REVISION 1 DATED 12/9/20. | | | | | | NOTE THAT THE AFFIDAVIT REFERS TO V1, V2, ETC. YOU | | | CANNOT USE PROJECTDOX VERSIONING FOR AFFIDAVITS, THERE | | | IS NO WAY TO SAVE VERSIONING. SO, I THINK BY V1 YOU | | | MEAN REVISION 1, V2 IS REVISION 2. IN THE FUTURE DO NOT | | | USE V1, V2, ETC. UNLESS THE PLAN REVISIONS ARE NAMED | | | V1, V2, ETC. | | | | | | 2. THE AFFIDAVIT FOR THE SUPPORTING DOCS REFERS TO | | | "NOA'S". REVISE THE AFFIDAVIT TO LIST THE NOAS THAT | | | WERE REVIEWED, OR PROVIDE NOAS THAT ARE STAMPED BY THE | | | PRIVATE PROVIDER AS REVIEWED. | | | | | | 3. ROOF ENHANCED FASTENING ENGINEERING IS NOT INCLUDED | | | IN THE AFFIDAVIT. | | | | | | | | | |
|