2020-11-30 12:41:3011/30/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CABANA BATH HAS THE WINE BAR SINK IN A WET
 CANNOT DISCHARGE INTO THE WET VET OF A BATHROOM GROUP
 IT MUST BE DOWNSTREAM PER THE 2017 FBC SECTION R3108.1
 HORIZONTAL WET VENT PERMITTED.
  
 2. IN MASTER PLEASE PROVIDE A VENT BETWEEN BOTH WATER
 CLOSETS PER THE 2017 FBC SEC. R 3101.2 TRAP SEAL
 PROTECTION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  