| Plan Review Notes For Permit 20110521 |
| Permit Number |
20110521 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-30 12:41:30 | 11/30/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. THE CABANA BATH HAS THE WINE BAR SINK IN A WET | | | CANNOT DISCHARGE INTO THE WET VET OF A BATHROOM GROUP | | | IT MUST BE DOWNSTREAM PER THE 2017 FBC SECTION R3108.1 | | | HORIZONTAL WET VENT PERMITTED. | | | | | | 2. IN MASTER PLEASE PROVIDE A VENT BETWEEN BOTH WATER | | | CLOSETS PER THE 2017 FBC SEC. R 3101.2 TRAP SEAL | | | PROTECTION. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|