Plan Review Notes
Plan Review Notes For Permit 20110521
Permit Number 20110521
Review Stop M
Sequence Number 1
Notes
Date Text
2020-11-19 10:43:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110521
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) HVAC LOADS CALCULATIONS INDICATES THAT BEDROOM #3 IS
 BEING SUPPLIED WITH 101 CFM OF CONDITIONED AIR. THE
 DRAWINGS INDICATE THIS SAME BEDROOM BEING SUPPLIED WITH
 10 CFM OF CONDITIONED AIR. PLEASE CORRECT DRAWINGS. FBC
 107.2
  
 2) SHEET M.2; EQUIPMENT SCHEDULE- THERE ARE 2
 MECHANICAL SYSTEMS FOR THIS PROJECT. SYSTEM # COLUMN
 INDICATE BOTH UNITS ARE 1,PLEASE IDENTIFY EACH AS AHU-1
 AND AHU-2 AS SHOWING ON THE DRAWINGS. FBC 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  