| 2020-12-01 14:33:18 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: FAILED. |
| | |
| | 1) PLEASE SHOW LOCATION OF NEW OUTSIDE PANEL AND |
| | IDENTIFY NEW ELECTRICAL PANEL A FBC 107 |
| | 2) GFCI, WP RECEPTACLE REQUIRED AT THE FRONT AND BACK |
| | OF THE DWELLING NEC 210.52(E) |
| | 3) NOTE 1 MENTIONS ?GROUNDING CONDUCTORS REQUIRED AT |
| | SWITCH LOCATIONS PER NEC 404.2?. ARTICLE 404.2 OF NEC |
| | DOES NOT TALK ABOUT OR REFER TO GROUNDING CONDUCTORS |
| | REQUIRED AT SWITCH LOCATIONS. |
| | 4) SPECIFY AVAILABLE FAULT CURRENT AT PANELS FBC 107 |
| | 5) EQUIPOTENTIAL POOL BONDING REQUIRED - NEC 680.26 |
| | 6) POOL RECEPTACLE REQUIRED - NEC 680-22 |
| | |
| | PLEASE CLARIFY AND CORRECT. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | SINCERELY, |
| | |
| | ENRIQUE QUINONEZ |
| | ELECTRICAL PLANS EXAMINER |