| 2020-11-30 15:38:11 | 11/30/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT A HOUSE PLAN SHOWING THE LOCATION OF THE |
| | TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF |
| | ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| | HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 2. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR TANKLESS GAS EQUIPMENT |
| | TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| | |
| | 3. ON SHEET P1.01 IT SHOWS TWO TANKLESS IN SERIES BUT |
| | ON ISOMETRIC THEY ARE 120? APART, PLEASE SHOW DETAIL |
| | WITH ONLY ONE UNIT PER THE WPB AMENDMENTS TO FBC |
| | SEC.107.2.1. |
| | |
| | 4. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2. |
| | |
| | 5. GAS UNITS REQUIRE CONDENSATE AND THEY NEED TO BE 1' |
| | AWAY FROM STRUCTURE PER THE 2017 FBC SEC R318.5. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |