Plan Review Notes
Plan Review Notes For Permit 20110518
Permit Number 20110518
Review Stop E
Sequence Number 1
Notes
Date Text
2020-12-09 08:18:10PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: VALUE HAS BEEN INCREASED BASED ON THE ICC
 BUILDING VALUATION TABLES AS FOLLOWS:
 NEW CONDITIONED SPACE - 709 SQ/FT @ $123.68 PER SQ/FT =
 $87,689
 NEW STORAGE (GARAGE) - 709 SQ/FT @ $62.20 PER SQ/FT =
 $44,100
 NEW UTILITY (COVERED PATIO - 400 SQ/FT AND BREEZEWAY -
 70 SQ/FT) - 470 SQ/FT @ $48.79 PER SQ/FT = $22,931
 TOTAL VALUE = $154,720
  
 1. PROVIDE GFCI OUTLET AT COVERED PATIO.
 PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE OUTLET
 FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING UNIT. NEC
 210.52(E)(3); FBC RE E3901.7
  
 2.PROVIDE OUTLETS AT WET BAR AREA.
 E3901.4.1 WALL COUNTERTOP SPACE.
 A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM),
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. [210.52(C)(1)]
  
 3. PROVIDE GFCI OUTLET AT BATHROOM LAV'S.
 E3901.6 BATHROOM.
 AT LEAST ONE WALL RECEPTACLE OUTLET SHALL BE INSTALLED
 IN BATHROOMS AND SUCH OUTLET SHALL BE LOCATED WITHIN 36
 INCHES (914 MM) OF THE OUTSIDE EDGE OF EACH LAVATORY
 BASIN.
  
 4. SMOKE ALARM REQUIRED AT EACH LEVEL.
 PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. FBC
 R R314.3
  
 5. OUTLET SPACING IN LIVING AREA.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET.
 PROVIDE CORRECTION. NEC 210.52; FBC RE E3901.2.1
  
 6. PROVIDE OUTLETS FOR MINI FRIDGE AND MICROWAVE.
 E3901.3 SMALL APPLIANCE RECEPTACLES.
 IN THE KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR
 SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE
 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 SECTION E3703.2, SHALL SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS COVERED BY SECTIONS E3901.2 AND
 E3901.4 AND THOSE RECEPTACLE OUTLETS PROVIDED FOR
 REFRIGERATION APPLIANCES. [210.52(B)(1)]
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  
  
  
  