| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2014 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: VALUE HAS BEEN INCREASED BASED ON THE ICC |
| | BUILDING VALUATION TABLES AS FOLLOWS: |
| | NEW CONDITIONED SPACE - 709 SQ/FT @ $123.68 PER SQ/FT = |
| | $87,689 |
| | NEW STORAGE (GARAGE) - 709 SQ/FT @ $62.20 PER SQ/FT = |
| | $44,100 |
| | NEW UTILITY (COVERED PATIO - 400 SQ/FT AND BREEZEWAY - |
| | 70 SQ/FT) - 470 SQ/FT @ $48.79 PER SQ/FT = $22,931 |
| | TOTAL VALUE = $154,720 |
| | |
| | 1. PROVIDE GFCI OUTLET AT COVERED PATIO. |
| | PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE OUTLET |
| | FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING UNIT. NEC |
| | 210.52(E)(3); FBC RE E3901.7 |
| | |
| | 2.PROVIDE OUTLETS AT WET BAR AREA. |
| | E3901.4.1 WALL COUNTERTOP SPACE. |
| | A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| | ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM), |
| | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| | SPACE. [210.52(C)(1)] |
| | |
| | 3. PROVIDE GFCI OUTLET AT BATHROOM LAV'S. |
| | E3901.6 BATHROOM. |
| | AT LEAST ONE WALL RECEPTACLE OUTLET SHALL BE INSTALLED |
| | IN BATHROOMS AND SUCH OUTLET SHALL BE LOCATED WITHIN 36 |
| | INCHES (914 MM) OF THE OUTSIDE EDGE OF EACH LAVATORY |
| | BASIN. |
| | |
| | 4. SMOKE ALARM REQUIRED AT EACH LEVEL. |
| | PROVIDE SMOKE ALARM ON EACH STORY OF THE DWELLING. FBC |
| | R R314.3 |
| | |
| | 5. OUTLET SPACING IN LIVING AREA. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. |
| | PROVIDE CORRECTION. NEC 210.52; FBC RE E3901.2.1 |
| | |
| | 6. PROVIDE OUTLETS FOR MINI FRIDGE AND MICROWAVE. |
| | E3901.3 SMALL APPLIANCE RECEPTACLES. |
| | IN THE KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR |
| | SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE |
| | 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY |
| | SECTION E3703.2, SHALL SERVE ALL WALL AND FLOOR |
| | RECEPTACLE OUTLETS COVERED BY SECTIONS E3901.2 AND |
| | E3901.4 AND THOSE RECEPTACLE OUTLETS PROVIDED FOR |
| | REFRIGERATION APPLIANCES. [210.52(B)(1)] |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |