Plan Review Notes
Plan Review Notes For Permit 20110518
Permit Number 20110518
Review Stop B
Sequence Number 1
Notes
Date Text
2020-12-07 15:12:17SFR DETACHED GARAGE/LIVING UNIT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE REQUIRED FLOOD VENT SIZES AND
 LOCATIONS TO COMPLY WITH FBC R322.2.2 ( THE DESIGN
 FLOOD ELEVATION IS 8.00 NAVD - CITY ORDINANCE REQUIRES
 2 FOOT ABOVE THE BASE FLOOD ELEVATION)
 2) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE STANDING SEAM METAL PANEL
 ROOFING SYSTEM - REVIEWED AND MARKED APPROVED BY THE
 BUILDING DESIGNER OF RECORD.
 3) ON THE ROOF FRAMING PLAN - PLEASE SHOW THE LOCATION
 OF THE STRAPPING PER THE CONNECTOR SCHEDULE SHOWN ON
 THE ROOF FRAMING PLAN.
 4) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT FROM
 AN ARCHITECT OR ENGINEER.
  