| Date |
Text |
| 2021-07-13 14:00:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE NO INDICATIONS,NUMBERED NARRATIVE NOR |
| | CLOUD REVISIONS ADDRESSING THE PREVIOUS FIRE COMMENTS |
| | |
| | PLEASE PROVIDE A DETAILED RESPONSE TO EACH COMMENT |
| | EITHER IN NARRATIVE FORM OR LABELED CLOUD REVISIONS ON |
| | THE PALN SHEETS. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | ******************************************************* |
| | ******************************************************* |
| | ************************* |
| | |
| | THE PREVIOUS COMMENTS ARE PROVIDED BELOW FOR REFERENCE |
| | PURPOSES: |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN ELECTRIC PUMP INDICATED; HOWEVER, THERE |
| | IS NO INDICATION THAT THE GENERATOR IS TIED INTO THIS |
| | PUMP. |
| | |
| | PLEASE REVIEW AND PROVIDE CLARIFICATION OR CORRECT. |
| | |
| | |
| | 2) THERE APPEARS TO BE FIRE SPRINKLER HEADS AT THE TOP |
| | OF THE ELEVATOR SHAFT. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE |
| | REQUIRED IN ELEVATOR |
| | MACHINE ROOMS, ELEVATOR MACHINERY SPACES, CONTROL |
| | SPACES, OR |
| | HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE |
| | WITH THE |
| | APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE |
| | BUILDING |
| | CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL |
| | ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR |
| | IS |
| | DEDICATED TO ELEVATOR EQUIPMENT ONLY. |
| | (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY |
| | SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF |
| | TRACTION |
| | ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER |
| | AUTOMATIC |
| | FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA72. |
| | (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL |
| | SPACE, |
| | OR HOISTWAY OF TRACTION ELEVATORS IS SEPARATED FROM THE |
| | REMAINDER |
| | OF THE BUILDING BY WALLS AND FLOOR/CEILING OR ROOF/ |
| | CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF |
| | NOT LESS |
| | THAN THAT SPECIFIED BY THE APPLICABLE BUILDING CODE. |
| | (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE |
| | PERMITTED |
| | TO BE STORED IN ELEVATOR MACHINE ROOMS, MACHINERY |
| | SPACES, CONTROL ROOMS, CONTROL SPACES, OR HOISTWAYS OF |
| | TRACTION |
| | ELEVATORS. |
| | (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC |
| | TYPE. |
| | |
| | 8.15.5.4* AUTOMATIC SPRINKLERS IN ELEVATOR MACHINE |
| | ROOMS OR |
| | AT THE TOPS OF HOISTWAYS SHALL BE OF ORDINARY- OR |
| | INTERMEDIATETEMPERATURE |
| | RATING. |
| | |
| | 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY |
| | SPRINKLERS SHALL |
| | BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS. |
| | |
| | 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE |
| | ELEVATOR HOISTWAY |
| | BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY |
| | FOR PASSENGER |
| | ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND |
| | THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF |
| | ASME |
| | A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. |
| | |
| | PLEASE REVIEW AND REMOVE OR PROVIDE DETAILS FOR THE |
| | REQUIRED FSH AT THE TOP OF THE SHAFT. |
| | |
| | |
| | |
| | 3) THERE ARE FIRE SPRINKLER HEADS INDICATED IN |
| | ELECTRICAL ROOMS WITH HIGH VOLTAGE WITH WALLS OF A 2 HR |
| | FIRE PROTECTION RATING. |
| | |
| | PER NFPA 13 ROOMS MEETING CERTAIN REQUIRMENTS MAY HAVE |
| | FIRE SPRINKLER PROTECTION OMITTED. |
| | |
| | 8.15.11.3 SPRINKLERS SHALL NOT BE REQUIRED IN |
| | ELECTRICAL EQUIPMENT |
| | ROOMS WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY. |
| | (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED. |
| | (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED |
| | ENCLOSURE |
| | INCLUDING PROTECTION FOR PENETRATIONS. |
| | (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN |
| | THE |
| | ROOM. |
| | |
| | PLEASE REVIEW AND IF EOR AGREES, THESE ROOMS MAY HAVE |
| | THEIR PROTECTION OMITTED. |
| | |
| | |
| | |
| | 4) THERE ARE INDICATIONS OF FIRE LINE UNDERGROUND WORK. |
| | |
| | ALL WORK, INSTALLATION, TESTING AND INSPECTIONS SHALL |
| | BE SUBMITTED AND COMPLETED UNDER SEPARATE PERMIT AND |
| | SHOP DRAWINGS. |
| | |
| | PLEASE ENSURE COMPLINACE AND PROVIDE A NOTE OF |
| | ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |