Plan Review Notes
Plan Review Notes For Permit 20110498
Permit Number 20110498
Review Stop M
Sequence Number 1
Notes
Date Text
2020-11-23 07:39:051ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110498
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1-01A ACCORDING TO THE APPROVED PLANS THERE
 ARE SEVERAL CHANGES AND OMISSIONS ON THIS SHEET THAT
 ARE NOT CLOUDED. PLEASE CLOUD ALL CHANGES ON THE NEW
 SHEETS. WHAT HAPPENED TO L-6 AND L-7? DUCTS FOR FUTURE
 HOOD SUPPLY AND EXHAUST IS NEW BUT NOT CLOUDED. PLEASE
 CLOUD ALL CHANGES FROM THE APPROVED PLANS. FBC 107.2
  
 2) SHEET M5-01 THE CLOUDS DO NOT APPEAR TO BE LOCATED
 IN THE RIGHT AREAS. THERE ARE CHANGES TO THE AIR DEVICE
 SCHEDULE THAT ARE NOT CLOUDED. THE LOUVER SCHEDULE
 NOTES HAVE CHANGED BUT NOT CLOUDED. WHY IS NOTE 4
 MISSING? ARE LOUVERS L-13 AND L-14 NOT BEING USED IN
 THE REVISED PLANS? FAN SCHEDULE NOTE 7 IS NOT ON THIS
 REVISED SHEET BUT IS NOT CLOUDED AS A CHANGE. IT IS
 UNCLEAR TO THE REVIEWER IF THIS WAS A MISTAKE OR IS NO
 LONGER NEEDED. PLEASE ADDRESS THIS. WHY WAS THE ASHRAE
 62.1-2013 VENTILATION RATE CALCULATIONS REMOVED ON THIS
 REVISION?
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  