| Date |
Text |
| 2020-11-17 07:03:53 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20110495 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE MECHANICAL EQUIPMENT HEATING AND |
| | COOLING SIZING. FBC EC C403.2.1 |
| | |
| | 2) THE SQUARE FOOTAGE IS OFF ON SHEETS A0.03 AND M6.1. |
| | PLEASE PROVIDE AN OUTDOOR AIR CALCULATION BASED ON THE |
| | ARCHITECTURAL SQUARE FOOTAGE AND THE OCCUPANT LOAD |
| | BASED ON THAT. FBC M 403.3.1.1 |
| | |
| | 3) PLEASE SHOW FIRE DAMPERS FOR THE RATED WALL |
| | PENETRATIONS OF THE EXISTING DUCTWORK. FBC M 607.5 |
| | |
| | 4) SHEET A0.03 INDICATES RATED WALLS AT ROOMS- O.FILES, |
| | S STORAGE AND WAITING. PLEASE SHOW FIRE DAMPERS AT EACH |
| | LOCATION THAT DUCT WORK PENETRATES THESE WALLS. FBC M |
| | 607.5 |
| | |
| | 5) PLEASE SHOW FIRE DAMPERS IN ALL LOCATIONS WHERE THE |
| | DUCTWORK PENETRATES A RATED WALL. FBC M 607.5 |
| | |
| | 6) PROVIDE A MECHANICAL DEMO SHEET THAT INCLUDES THE |
| | EXISTING DUCTWORK SIZES. FBC 107.2 |
| | |
| | 7) AREA ABOVE CEILING IS CONSIDERED A PLENUM, PLEASES |
| | MAKE SURE ALL TRADES ARE AWARE. FBC M 602.2.1MATERIALS |
| | WITHIN PLENUMS. |
| | EXCEPT AS REQUIRED BY SECTIONS 602.2.1.1 THROUGH |
| | 602.2.1.7, MATERIALS WITHIN PLENUMS SHALL BE |
| | NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING |
| | A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E84 OR UL 723. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |