| 2020-11-18 14:29:53 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20110495 |
| | ADD: 625 N. FLAGLER DR. / 10TH FLOOR |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-615-3903 / MICHAEL MCCLOSKEY |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. /NOV. 18TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A0.02 PLEASE INDICATE IF THERE IS ANY WORK TO |
| | BE COMPLETED UNDER THIS PERMIT FOR THE 1ST FLOOR, OR |
| | WAS IT SUBMITTED FOR LIFE SAFETY CONCERNS IN EXITING? |
| | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. SHEET |
| | A1.10 GROUND FLOOR CONSTRUCTION NOTE ONE INDICATES A |
| | NEW ELECTRONIC ROLL-UP DOOR AND ACCESS CONTROL SYSTEM. |
| | WHAT THE 1ST FLOOR LIFE SAFETY PLAN DOES NOT SHOW IS |
| | HOW ONCE THE OCCUPANTS LEAVE THE 2 HOUR EXIT HOW THEY |
| | ARE GOING TO BE ABLE TO TRAVEL TO THE PUBLIC WAY? 2017 |
| | FBC-B 1028.5 ACCESS TO A PUBLIC WAY. |
| | |
| | 2) SHEET A0.03 LIFE SAFETY PLAN 10TH FLOOR SUITE: 1001: |
| | |
| | 2A) UNDER THE HEADING CODE REQUIREMENTS THE LISTING |
| | EXIT ACCESS DOORWAYS, PLANS INDICATE 1 REQUIRED, 2 |
| | PROVIDED AND SECTION TABLE 1006.2.1. PLEASE BE AWARE |
| | THAT TABLE 1006.2.1 IS TO BE USED FOR THE GRADE FLOOR |
| | ONLY. TABLE 1006.3.2(1) IS FOR R-2 OCCUPANCIES 1ST-3RD |
| | FLOOR, AND TABLE 1006.3.2(2) IS TO BE USED FOR LISTED |
| | OCCUPANCIES FOR STORIES FIRST FLOOR ABOVE OR BELOW |
| | GRADE PLANE AND THE 2ND STORY ABOVE GRADE PLANE. ALSO |
| | REVIEW SECTION 1006.3 OF THE 2017 FBC-BUILDING. |
| | |
| | 2B) EXIT ACCESS TRAVEL IS FOUND IN TABLE 1017.2 OF THE |
| | 2017 FBC-BUILDING. PLEASE UPDATE PLANS. |
| | |
| | 3) SHEET A4.22 SHOWS THE PEDESTRIAN GATE AND ELECTRONIC |
| | OVERHEAD ROLL-UP GARAGE DOOR, BOTH OF THESE WOULD |
| | APPEAR TO NEED PRODUCT APPROVALS AS WELL AS WIND DESIGN |
| | PRESSURES. THERE ARE NO STRUCTURAL DETAILS OF HOW THE |
| | ROLL UP OVERHEAD DOOR IS TO BE ANCHORED FOR THE DOOR |
| | ASSEMBLY ITSELF NOR THE TRACK SYSTEM FOR THE DOOR TO |
| | MOVE IN VERTICALLY. THE SAME REQUIREMENTS ARE MISSING |
| | FOR THE PEDESTRIAN GATE. THE PEDESTRIAN GATE IS A ONE |
| | TYPE OF FABRICATION I WOULD BELIEVE AND WOULD ONLY |
| | REQUIRE THE ENGINEERING FOR THIS TYPE OF INSTALLATION |
| | AND EXPOSURE. |
| | |
| | 3A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 2. RISK CATEGORY. |
| | |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 3B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS. |
| | |
| | 3C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 3D) WITHOUT STRUCTURAL DETAILS FOR THE 2 NEW PRODUCTS |
| | DOOR OPENINGS THIS MAY OR MAY NOT BE REQUIRED. |
| | WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| | WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| | REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF |
| | FRAMING INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |