| Plan Review Notes For Permit 20110455 |
| Permit Number |
20110455 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-12 16:52:34 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GARAGE DOOR OPENING IS ALSO ONE OF THE TWO | | | REQUIRED FLOOD OPENINGS REQUIRED FOR THIS PROJECT. IN | | | ADDITION TO THE 913 SQUARE INCH NET OPENING (ALLOWING | | | FOR GRATE) ON THE NORTH WALL THERE IS 9, 273 SQUARE | | | INCHES OF OPENING BELOW THE DESIGN FLOOD ELEVATION | | | (DFE) THAT IS COUNTED TOWARD THE REQUIRED AREA OF FLOOD | | | VENT OPENINGS. SEE ARCHITECTURAL SHEET A2.1 OF THE | | | PLANS FOR NOTES ON THE FLOOD VENT OPENINGS. |
|