| 2020-11-25 14:43:49 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20110453 |
| | 11/25/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 1: THE UG LP TANK INSTALLATION DETAIL HAS A |
| | COPIED ENGINEER'S SEAL AND SIGNATURE FROM 7/11/10. |
| | PLEASE SUBMIT AN UPDATED DOCUMENT WITH A DIGITAL SEAL |
| | AND SIGNATURE, OR IF THE EOR DOES NOT HAVE A DIGITAL |
| | SEAL AND SIGNATURE, A HARD PAPER COPY WITH A RAISED OR |
| | INK SEAL AND WET SIGNATURE CAN BE DROPPED OFF IN THE |
| | DROP BOX AT WPB CITY HALL, BUILDING DIVISION 1ST FLOOR. |
| | PLEASE PROVIDE A PLAN REVIEW REQUEST FORM WITH THE |
| | SIGNED AND SEALED DOCUMENT- FL. STATUTE 471.025 AND |
| | SECTIONS 61G15-23.002-23.005 FAC. PLEASE UPDATE THE |
| | DETAIL TO SHOW HOW THE TANK WILL BE PROTECTED FROM |
| | ABRASION AND CORROSION FROM THE TIE DOWN CABLES. |
| | |
| | 2) THE SIGNATURE AND THE PRINTED NAME OF THE |
| | CONTRACTOR, AND THE PROJECT ADDRESS SHALL BE ON THE GAS |
| | RISER DRAWING- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |