| Plan Review Notes For Permit 20110431 |
| Permit Number |
20110431 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-19 09:56:09 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | REVIEW STATUS: FAILED. | | | | | | 1) PERMIT AND DIAGRAM MENTION INSTALLATION OF NEW WATER | | | HEATER BUT LOAD CALCULATIONS SHOW NEW LOADS FOR A POOL | | | PUMP AND POOL LIGHTS AND WATER HEATER IS NOT MENTIONED. | | | PLEASE CLARIFY AND CORRECT. | | | 2) ON DIAGRAM, PLEASE SPECIFY SIZE OF CONDUCTOR AND | | | BREAKER FEEDING THE NEW WATER HEATER. | | | | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|