| 2020-12-02 14:41:10 | TEMPORARY TRAILER |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE PROVIDE THE TRAILER "STATE APPROVAL" DRAWINGS |
| | REVIEWED AND APPROVED BY A 3RD PARTY FBC 107.3 |
| | EXCEPTION (1). |
| | 2) PLEASE PROVIDE TRAILER TIE DOWN DETAILS FROM AN |
| | ARCHITECT OR ENGINEER TO COMPLY WITH WIND LOADS PER FBC |
| | 1609 (SHOW THE WIND DESIGN CRITERIA USED ON THE |
| | DRAWING) |
| | 3) PLEASE PROVIDE STAIR, RAMP AND HANDRAIL DETAILS TO |
| | COMPLY WITH FBC CHAPTER 10 AND FBC ACCESSIBILITY |
| | REQUIREMENTS. |
| | 4) PLEASE PROVIDE GUARD RAIL DETAILS IF REQUIRED PER |
| | FBC 1015.2 |
| | 5) PLEASE SHOW THE DISTANCE FROM THE EXISTING BUILDINGS |
| | TO COMPLY WITH FBC 602 (BASED ON THE TRAILER |
| | CONSTRUCTION TYPE AND WALL FIRE RATINGS) |
| | 6) PLEASE SHOW THE DOOR MANEUVERING CLEARANCE (IN AND |
| | OUT OF THE EXISTING BUILDING) TO COMPLY WITH FBC |
| | ACCESSIBILITY 404.2.4 (WHICH SHALL BE A LEVEL LANDING |
| | PER FBC 404.2.4.4) |
| | 7) PLEASE DESCRIBE THE USE FOR THE TRAILER TO HELP |
| | DETERMINE THE OCCUPANCY CLASSIFICATION - USE, QUANTITY |
| | OF HAZARDOUS CHEMICALS ETC. |
| | 8) PLEASE PROVIDE SIGNED AND SEALED CONCRETE DECK, |
| | RETAINING WALLS AND PAD DETAILS FROM AN ARCHITECT OR |
| | ENGINEER. |
| | 9) PLEASE PROVIDE SIGNED AND SEALED CANOPY DETAILS FROM |
| | AN ARCHITECT OR ENGINEER TO COMPLY WITH THE WIND LOADS |
| | PER FBC 3105.3 AND 1609 (SHOW THE WIND DESIGN CRITERIA |
| | USED ON THE DRAWINGS) - 3105.3.4.1 FABRIC USED FOR |
| | AWNINGS OR FABRIC-COVERED FRAMES SHALL MEET THE FLAME |
| | PROPAGATION PERFORMANCE CRITERIA OF NFPA 701 OR HAVE A |
| | FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E84 OR UL 723. |
| | 10) PLEASE PROVIDE THE FRONT PAGES OF THE FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE PROVIDED INSTALLATION |
| | DRAWINGS FOR THE STOREFRONT WINDOWS AND DOOR. |
| | 11) PLEASE SHOW THE REQUIRED DESIGN WIND PRESSURES TO |
| | BE USED FOR EXTERIOR COMPONENT (AREA OF NEW DOOR) FBC |
| | 1603.1.4 |
| | |