| Date |
Text |
| 2021-04-19 18:36:07 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110398 |
| | 4/19/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| | WITH ADDITIONAL NOTES. |
| | |
| | 4) FAILED. P2.2: REFER TO SECTION 803.1 FBC P AND |
| | PROVIDE DILUTION OR NEUTRALIZING DEVICES FOR ANY |
| | CENTRAL STERILE WORKROOM AND STORAGE FIXTURES OR |
| | EQUIPMENT DISCHARGING CORROSIVE LIQUIDS, ACIDS OR |
| | CHEMICALS THAT COULD DAMAGE THE DRAINAGE SYSTEM OR |
| | CREATE NOXIOUS OR TOXIC FUMES. THE PLANS SHOW EYE WASH |
| | STATIONS WHICH ARE TYPICALLY REQUIRED FOR EXPOSURE TO |
| | CORROSIVE MATERIALS. THE ARCHITECT IS STATING IN HIS |
| | RESPONSE THAT ACCORDING TO THE MEDICAL EQUIPMENT |
| | SUPPLIER THE FIXTURES OR EQUIPMENT DO NOT DISCHARGE |
| | CORROSIVE LIQUIDS OR ACIDS OR DAMAGING CHEMICALS ETC., |
| | HOWEVER EYE WASH STATIONS ARE BEING INSTALLED. PLEASE |
| | NOTE THAT SHEET EQ300 WHICH IS THE MEDICAL EQUIPMENT |
| | PLAN HAS NOT BEEN SUBMITTED. THE PLANS ALSO INDICATE |
| | INSTALLATION OF CHEMICAL RESISTANT PVDF PIPING FOR THE |
| | R0/DI SYSTEM. AT THIS TIME MORE INFORMATION AND |
| | EVIDENCE IS REQUIRED TO DETERMINE IF COMPLIANCE WITH |
| | SECTION 803.1 WILL APPLY. |
| | THE OSHA REQUIREMENTS FOR EMERGENCY EYEWASHES AND |
| | SHOWERS, FOUND AT 29 CFR 1910.151(C), SPECIFY THAT |
| | "WHERE THE EYES OR BODY OF ANY PERSON MAY BE EXPOSED TO |
| | INJURIOUS CORROSIVE MATERIALS, SUITABLE FACILITIES FOR |
| | QUICK DRENCHING OR FLUSHING OF THE EYES AND BODY SHALL |
| | BE PROVIDED WITHIN THE WORK AREA FOR IMMEDIATE |
| | EMERGENCY USE. AS THE STANDARD STATES, AN EYEWASH |
| | AND/OR SAFETY SHOWER WOULD BE REQUIRED WHERE AN |
| | EMPLOYEE'S EYES OR BODY COULD BE EXPOSED TO INJURIOUS |
| | CORROSIVE MATERIALS. |
| | |
| | 7) FAILED. P2.2, P4.2: PROVIDE CENTRAL STERILE NP AND |
| | PW PIPING SPECIFICATIONS- SECTION 107.2.1 WPB. PLEASE |
| | PROVIDE NON-POTABLE SPECIFICATIONS AND SIGNAGE |
| | REQUIRMENTS ON THE PLAN: |
| | SECTION 608.9.2 DISTRIBUTION PIPE LABELING AND |
| | MARKING.NONPOTABLE DISTRIBUTION PIPING SHALL BE PURPLE |
| | IN COLOR AND SHALL BE EMBOSSED, OR INTEGRALLY STAMPED |
| | OR MARKED, WITH THE WORDS: 'CAUTION: NONPOTABLE WATER ' |
| | DO NOT DRINK' OR THE PIPING SHALL BE INSTALLED WITH A |
| | PURPLE IDENTIFICATION TAPE OR WRAP. PIPE IDENTIFICATION |
| | SHALL INCLUDE THE CONTENTS OF THE PIPING SYSTEM AND AN |
| | ARROW INDICATING THE DIRECTION OF FLOW. HAZARDOUS |
| | PIPING SYSTEMS SHALL ALSO CONTAIN INFORMATION |
| | ADDRESSING THE NATURE OF THE HAZARD. PIPE |
| | IDENTIFICATION SHALL BE REPEATED AT INTERVALS NOT |
| | EXCEEDING 25 FEET (7620 MM) AND AT EACH POINT WHERE THE |
| | PIPING PASSES THROUGH A WALL, FLOOR OR ROOF. LETTERING |
| | SHALL BE READILY OBSERVABLE WITHIN THE ROOM OR SPACE |
| | WHERE THE PIPING IS LOCATED. |
| | 608.9 IDENTIFICATION OF NONPOTABLE WATER SYSTEMS. |
| | WHERE NONPOTABLE WATER SYSTEMS ARE INSTALLED, THE |
| | PIPING CONVEYING THE NONPOTABLE WATER SHALL BE |
| | IDENTIFIED EITHER BY COLOR MARKING, METAL TAGS OR TAPE |
| | IN ACCORDANCE WITH SECTIONS 608.9.1 THROUGH 608.9.2.3. |
| | |
| | 608.9.1SIGNAGE REQUIRED. |
| | NONPOTABLE WATER OUTLETS, SUCH AS HOSE CONNECTIONS, |
| | OPEN ENDED PIPES AND FAUCETS, SHALL BE IDENTIFIED WITH |
| | SIGNAGE THAT READS AS FOLLOWS: 'NONPOTABLE WATER IS |
| | UTILIZED FOR [APPLICATION NAME]. CAUTION: NONPOTABLE |
| | WATER ' DO NOT DRINK.' THE WORDS SHALL BE LEGIBLY AND |
| | INDELIBLY PRINTED ON A TAG OR SIGN CONSTRUCTED OF |
| | CORROSION-RESISTANT WATERPROOF MATERIAL OR SHALL BE |
| | INDELIBLY PRINTED ON THE FIXTURE. THE LETTERS OF THE |
| | WORDS SHALL BE NOT LESS THAN 0.5 INCH IN HEIGHT AND IN |
| | COLORS IN CONTRAST TO THE BACKGROUND ON WHICH THEY ARE |
| | APPLIED. IN ADDITION TO THE REQUIRED WORDAGE, THE |
| | PICTOGRAPH SHOWN IN FIGURE 608.9.1 SHALL APPEAR ON THE |
| | REQUIRED SIGNAGE. |
| | |
| | 9) FAILED. A3.1: THE DOOR SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE OF THE SHOWER- SECTION 603.2.3 FBC |
| | ACC. SHEET A3.1A SHOWS THE DOOR SWINGING INTO THE CLEAR |
| | FLOOR SPACE OF THE SHOWER. |
| | |
| | 11) FAILED. A0.2 & A3.1: PROVIDE DETAILS SHOWING SHOWER |
| | SEAT POSITIONING, LENGTHS, AND MOUNTING HEIGHTS- |
| | SECTION 608.4 & 610.3 FBC ACC. REFER TO SECTION AND |
| | FIGURE 610.3.2 L-SHAPED SEATS- PROVIDE A DIMENSIONED |
| | SEAT DETAIL ON THE PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |