| 2020-12-18 18:11:12 | |
| | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110398 |
| | 12/18/20 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P0.1, P1.1, & P: PLEASE NOTE SEPARATE PERMIT |
| | APPLICATIONS AND PLAN SUBMITTALS ARE REQUIRED FOR |
| | INSTALLATION OF THE BACKFLOW PREVENTER AND THE MEDICAL |
| | GAS SYSTEM ALTERATIONS- SECTION 105.1 & 107.2.1 WPB. |
| | |
| | A) A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | B) A FL. LICENSED PLUMBER HOLDING A MEDICAL GAS PIPING |
| | INSTALLATION OBTAINED IN ACCORDANCE WITH FL. STATUTE |
| | 489.1136 CERTIFICATE SHALL SUBMIT A SEPARATE PRIMARY |
| | APPLICATION AND COMPLETE PLANS FOR THE MED GAS SYSTEM |
| | ALTERATIONS. |
| | |
| | 2) P2.2: NOTE-8- SHOW THE POINT OF CONNECTION FOR THE |
| | NEW 1? NPSCW AT STERILIZER TO THE EXISTING LINE- |
| | SECTION 107.2.1 WPB. |
| | |
| | 3) P2.2: PLEASE PROVIDE AN ENLARGED TYPICAL INDIRECT |
| | WASTE DISCHARGE DETAIL FOR THE 3-COMPARTMENT SINKS IN |
| | THE SOILED WORKROOM, AND SCOPE ROOM; AND PROVIDE A |
| | TYPICAL INDIRECT WASTE DETAIL FOR ALL OTHER FLOOR SINKS |
| | LOCATED BELOW THE STERILIZER AND OTHER CENTRAL STERILE |
| | WORKROOM AND STORAGE FIXTURES AND EQUIPMENT- SECTION |
| | 713.3 FBC P. |
| | |
| | 4) P2.2: REFER TO SECTION 803.1 FBC P AND PROVIDE |
| | DILUTION OR NEUTRALIZING DEVICES FOR ANY CENTRAL |
| | STERILE WORKROOM AND STORAGE FIXTURES OR EQUIPMENT |
| | DISCHARGING CORROSIVE LIQUIDS, ACIDS OR CHEMICALS THAT |
| | COULD DAMAGE THE DRAINAGE SYSTEM OR CREATE NOXIOUS OR |
| | TOXIC FUMES. |
| | |
| | 5) P2.2, P2.3, P4.1: PROVIDE TRAP PRIMERS FOR FLOOR |
| | DRAINS AND FLOOR SINKS WITH SEALS SUBJECT TO |
| | EVAPORATION- SECTION 1002.4.1 FBC P. SHOW THE LOCATIONS |
| | ON THE PIPING PLAN AND ISOMETRIC DRAWING, AND PROVIDE A |
| | DETAIL. |
| | |
| | 6) P2.2: PLEASE INCLUDE THE FLOOR SINKS, FAUCETS, |
| | SPRAYERS, HOSES, VALVES, AND ALL OTHER PLUMBING |
| | FIXTURES AND DEVICES TO BE INSTALLED IN THE CENTRAL |
| | STERILE WORK AND STORAGE ROOMS- SECTION 107.2.1 WPB. |
| | |
| | 7) P2.2, P4.2: PROVIDE CENTRAL STERILE NP AND PW PIPING |
| | SPECIFICATIONS- SECTION 107.2.1 WPB. |
| | |
| | 8) P4.2: PROVIDE SYMBOLS TO SHOW THE WATER HAMMER |
| | ARRESTOR LOCATIONS- SECTION 604.9 FBC P. |
| | |
| | 9) A3.1: THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE OF THE SHOWER- SECTION 603.2.3 FBC ACC. |
| | |
| | 10) A0.2 & A3.1: PROVIDE DETAILS SHOWING SHOWER GRAB |
| | BAR POSITIONING, LENGTHS, AND MOUNTING HEIGHTS- SECTION |
| | 608.3.1 & 609.1 FBC ACC. |
| | |
| | 11) A0.2 & A3.1: PROVIDE DETAILS SHOWING SHOWER SEAT |
| | POSITIONING, LENGTHS, AND MOUNTING HEIGHTS- SECTION |
| | 608.4 & 610.3 FBC ACC. |
| | |
| | 12) A0.2 & A3.1: SHOW THE SHOWER CONTROL AND FAUCET |
| | LOCATIONS PER SECTION 608.5.1 FBC ACC. |
| | |
| | 13) A0.2: SHOW THE TOILET ROOM GRAB HEIGHTS FROM THE |
| | FINISHED FLOORS TO THE TOP OF THE GRIPPING SURFACES- |
| | SECTION 609.4 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |