| Plan Review Notes For Permit 20110398 |
| Permit Number |
20110398 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-24 14:38:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET FP 1.0 - THIS DRAWING IS INDICATED AS NOT | | | BEING UPLAODED PROPERLY AND DOES NOT SHOW UP. | | | | | | BE SURE TO INCLUDE THAT ANY FS WORK, INCLUDING DEMO, | | | SHALL BE SUBMITTED UNDER SEPARATE PERMIT AND SHOP | | | DRAWINGS | | | | | | PLEASE REVIEW AND UPLOAD SO IT IS VIEWABLE. | | | | | | | | | | | | 2) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF FIRE | | | ALARM WORK, INCLUDING DEMO. | | | | | | PLEASE REVIEW AND PROVIDE INDICATIONS OF FA WORK, | | | INCLUDING DEMO, UNDER SEPARATE PERMIT AND SHOP | | | DRAWINGS. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|