Plan Review Notes
Plan Review Notes For Permit 20110397
Permit Number 20110397
Review Stop P
Sequence Number 2
Notes
Date Text
2021-03-05 07:58:142ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20110397
 3/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 BASED ON THE RESUBMITTED PLANS AND NARRATIVBE RESPONSE,
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH NOTES IN CAP LETTERS ADDED FOR CLARIFICATION.
  
 1) FAILED. PLEASE PROVIDE SANITARY DRAINAGE AND WATER
 DISTRIBUTION ISOMETRIC DRAWINGS- SECTION 107.3.5.1.3
 WPB. SHEETS P2.0 & P6.0, CONFLICT WITH THE DRAWINGS:
 THE FLOOR DRAINS IN THE MECHANICAL ROOM SHOWN IN THE
 NEW ISOMETRIC (P6.0) HAVE BEEN REMOVED FROM THE FLOOR
 PLAN (P2.0). PLEASE CLARIFY WHAT THE DESIGN INTENTION
 IS, AND NOTE THAT BOILER ROOMS SHALL BE EQUIPPED WITH A
 FLOOR DRAIN OR OTHER APPROVED MEANS FOR DISPOSING OF
 LIQUID WASTE- SECTION 1004.6 FBC M. PLEASE NOTE THE WH
 DETAIL ON P.73 SHOWS FLOOR DRAINS.
  
 3) FAILED.P2.0, P5.1: PLEASE PROVIDE AN ENLARGED
 TYPICAL INDIRECT WASTE DISCHARGE DETAIL FOR THE
 3-COMPARTMENT SINKS IN THE SOILED WORKROOM, AND A
 TYPICAL INDIRECT WASTE DISCHARGE DETAIL FOR ALL OTHER
 FLOOR SINKS LOCATED UNDER CENTRAL STERILE EQUIPMENT AND
 FIXTURES- SECTION 713.3 FBC P. THE DETAIL ON P7.1 IS
 FOR A SINGLE INDIRECT WASTE DRAIN PIPE. PLEASE PROVIDE
 A 3-COMPARTMENT DRAIN DETAIL AS REQUESTED.
  
 6) FAILED. P0.1, P2.1, P5.1: PLEASE PROVIDE A SCHEDULE
 FOR THE REQUIRED BACKFLOW PREVENTERS TO BE INSTALLED ON
 SUPPLY LINES TO THE STERILIZERS, RO GENERATOR AND ALL
 OTHER PLUMBING FIXTURES PERFORMING A SPECIAL FUNCTION-
 SEE SECTIONS 422.2, 608.3, AND TABLE 608.1 FBC P.
 PLEASE SHOW THE BACKFLOW PREVENTER LOCATIONS ON THE
 PLUMBING PIPING PLANS AND ISOMETRIC DRAWING, AND
 PROVIDE AN INSTALLATION DETAIL. PLEASE SHOW LOCATION OF
 THE RO BF PREVENTER.
  
 8) FAILED. P0.1, P.2.1, P.51: PROVIDE ENLARGED WATER
 HEATER PIPING DETAILS SHOWING POTABLE WATER INLET AND
 OUTLET CONNECTIONS, PIPING CONNECTIONS TO RECIRCULATION
 PUMPS, BACKFLOW PREVENTERS- SECTION 502.1, 607.2, AND
 608.3 FBC P. PLEASE SHOW HOW STEAM CONDENSATION AND
 RELIEF VALVE DISCHARGE WILL BE DRAINED TO AN APPROVED
 LOCATION OR WASTE RECEPTOR-SECTION 314.2.1 AND 504.6
 FBC P. THE DETAIL ON SHEET P7.3 DOES NOT SHOW THERMAL
 EXPANSION TANKS FOR THE WATER HEATERS. PLEASE SEE
 MANUFACTURERS SPECIFICATIONS AND - SECTION 607.3 FBC P
 AND 1003.1 FBC M.
  
 12) ROOF AND STORM DRAINS- FBC P.
 C) FAILED. P2.2: PLEASE SHOW THE PRIMARY AND OVERFLOW
 SCUPPERS THAT ARE SHOWN ON SHEET A3.1- SECTION 107.2.1
 WPB AND 1101.7. NOT PROVIDED ON SHEET P2.2, AND ARE
 REQUIRED FOR PLUMBING COMPLIANCE.
 D) FAILED. PROVIDE SIZING CALCULATIONS FOR THE PRIMARY
 VERTICAL LEADERS AND HORIZONTAL BRANCHES BASED ON
 SECTIONS 1106.1 & 1106.2. REFER TO TABLE 1106.2 FBC P.
 PLEASE CLARIFY WHAT THE FIGURES IN PARENTHESES
 REPRESENT. REFER TO TABLE 1106.2 FOR GPM FLOW CAPACTIES
 OF STORM DRAIN PIPING AND PROVIDE CORRECT CALCULATIONS.
 E) FAILED. PROVIDE SIZING CALCULATIONS FOR THE
 SECONDARY ROOF DRAINS- SECTION 1108.3. NOT PROVIDED.
 SEE COMMENT 12D NOTES ABOVE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  