| 2021-03-05 07:58:14 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20110397 |
| | 3/5/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | BASED ON THE RESUBMITTED PLANS AND NARRATIVBE RESPONSE, |
| | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| | WITH NOTES IN CAP LETTERS ADDED FOR CLARIFICATION. |
| | |
| | 1) FAILED. PLEASE PROVIDE SANITARY DRAINAGE AND WATER |
| | DISTRIBUTION ISOMETRIC DRAWINGS- SECTION 107.3.5.1.3 |
| | WPB. SHEETS P2.0 & P6.0, CONFLICT WITH THE DRAWINGS: |
| | THE FLOOR DRAINS IN THE MECHANICAL ROOM SHOWN IN THE |
| | NEW ISOMETRIC (P6.0) HAVE BEEN REMOVED FROM THE FLOOR |
| | PLAN (P2.0). PLEASE CLARIFY WHAT THE DESIGN INTENTION |
| | IS, AND NOTE THAT BOILER ROOMS SHALL BE EQUIPPED WITH A |
| | FLOOR DRAIN OR OTHER APPROVED MEANS FOR DISPOSING OF |
| | LIQUID WASTE- SECTION 1004.6 FBC M. PLEASE NOTE THE WH |
| | DETAIL ON P.73 SHOWS FLOOR DRAINS. |
| | |
| | 3) FAILED.P2.0, P5.1: PLEASE PROVIDE AN ENLARGED |
| | TYPICAL INDIRECT WASTE DISCHARGE DETAIL FOR THE |
| | 3-COMPARTMENT SINKS IN THE SOILED WORKROOM, AND A |
| | TYPICAL INDIRECT WASTE DISCHARGE DETAIL FOR ALL OTHER |
| | FLOOR SINKS LOCATED UNDER CENTRAL STERILE EQUIPMENT AND |
| | FIXTURES- SECTION 713.3 FBC P. THE DETAIL ON P7.1 IS |
| | FOR A SINGLE INDIRECT WASTE DRAIN PIPE. PLEASE PROVIDE |
| | A 3-COMPARTMENT DRAIN DETAIL AS REQUESTED. |
| | |
| | 6) FAILED. P0.1, P2.1, P5.1: PLEASE PROVIDE A SCHEDULE |
| | FOR THE REQUIRED BACKFLOW PREVENTERS TO BE INSTALLED ON |
| | SUPPLY LINES TO THE STERILIZERS, RO GENERATOR AND ALL |
| | OTHER PLUMBING FIXTURES PERFORMING A SPECIAL FUNCTION- |
| | SEE SECTIONS 422.2, 608.3, AND TABLE 608.1 FBC P. |
| | PLEASE SHOW THE BACKFLOW PREVENTER LOCATIONS ON THE |
| | PLUMBING PIPING PLANS AND ISOMETRIC DRAWING, AND |
| | PROVIDE AN INSTALLATION DETAIL. PLEASE SHOW LOCATION OF |
| | THE RO BF PREVENTER. |
| | |
| | 8) FAILED. P0.1, P.2.1, P.51: PROVIDE ENLARGED WATER |
| | HEATER PIPING DETAILS SHOWING POTABLE WATER INLET AND |
| | OUTLET CONNECTIONS, PIPING CONNECTIONS TO RECIRCULATION |
| | PUMPS, BACKFLOW PREVENTERS- SECTION 502.1, 607.2, AND |
| | 608.3 FBC P. PLEASE SHOW HOW STEAM CONDENSATION AND |
| | RELIEF VALVE DISCHARGE WILL BE DRAINED TO AN APPROVED |
| | LOCATION OR WASTE RECEPTOR-SECTION 314.2.1 AND 504.6 |
| | FBC P. THE DETAIL ON SHEET P7.3 DOES NOT SHOW THERMAL |
| | EXPANSION TANKS FOR THE WATER HEATERS. PLEASE SEE |
| | MANUFACTURERS SPECIFICATIONS AND - SECTION 607.3 FBC P |
| | AND 1003.1 FBC M. |
| | |
| | 12) ROOF AND STORM DRAINS- FBC P. |
| | C) FAILED. P2.2: PLEASE SHOW THE PRIMARY AND OVERFLOW |
| | SCUPPERS THAT ARE SHOWN ON SHEET A3.1- SECTION 107.2.1 |
| | WPB AND 1101.7. NOT PROVIDED ON SHEET P2.2, AND ARE |
| | REQUIRED FOR PLUMBING COMPLIANCE. |
| | D) FAILED. PROVIDE SIZING CALCULATIONS FOR THE PRIMARY |
| | VERTICAL LEADERS AND HORIZONTAL BRANCHES BASED ON |
| | SECTIONS 1106.1 & 1106.2. REFER TO TABLE 1106.2 FBC P. |
| | PLEASE CLARIFY WHAT THE FIGURES IN PARENTHESES |
| | REPRESENT. REFER TO TABLE 1106.2 FOR GPM FLOW CAPACTIES |
| | OF STORM DRAIN PIPING AND PROVIDE CORRECT CALCULATIONS. |
| | E) FAILED. PROVIDE SIZING CALCULATIONS FOR THE |
| | SECONDARY ROOF DRAINS- SECTION 1108.3. NOT PROVIDED. |
| | SEE COMMENT 12D NOTES ABOVE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |