2020-12-17 16:31:051ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110397
 12/17/20
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SANITARY DRAINAGE AND WATER
 DISTRIBUTION ISOMETRIC DRAWINGS- SECTION 107.3.5.1.3
 WPB.
  
 2) SHEET P0.1: PLEASE PROVIDE A SCHEDULE FOR THE VENDOR
 SUPPLIED FIXTURES AND EQUIPMENT IN THE CENTRAL STERILE
 - TRIPLE BASIN PROCESSING SINKS, STEAM STERILIZERS, RO
 GENERATOR, WASHER/DISINFECTOR, CART WASHERS, SINK
 FAUCETS, SPRAYERS ETC. INCLUDE THE MAKES AND MODELS AND
 THE AGENCY LISTING APPROVAL NUMBERS- SECTION 422.1 &
 422.2 FBC P. PLEASE NOTE THAT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS FOR ALL
 PLUMBING FIXTURES, EQUIPMENT, AND DEVICES MAY BE
 DEFERRED SUBMITTALS OR BE ONSITE AT TIME OF INSPECTION-
 SECTIONS 107.2.1 AND 107.3.4.1 WPB.
  
 3) P2.0, P5.1: PLEASE PROVIDE AN ENLARGED TYPICAL
 INDIRECT WASTE DISCHARGE DETAIL FOR THE 3-COMPARTMENT
 SINKS IN THE SOILED WORKROOM, AND A TYPICAL INDIRECT
 WASTE DISCHARGE DETAIL FOR ALL OTHER FLOOR SINKS
 LOCATED UNDER CENTRAL STERIL EQUIPMENT AND FIXTURES-
 SECTION 713.3 FBC P.
  
 4) P2.0, P5.1: REFER TO SECTION 803.1 FBC P AND PROVIDE
 DILUTION OR NEUTRALIZING DEVICES FOR ANY CENTRAL
 STERILE FIXTURES OR EQUIPMENT DISCHARGING CORROSIVE
 LIQUIDS, ACIDS OR CHEMICALS THAT COULD DAMAGE THE
 DRAINAGE SYSTEM OR CREATE NOXIOUS OR TOXIC FUMES.
  
 5) P2.0, P5.1: PROVIDE TRAP PRIMERS FOR FLOOR SINKS
 WITH SEALS SUBJECT TO EVAPORATION- SECTION 1002.4.1 FBC
 P. SHOW THE LOCATIONS ON THE PIPING PLAN AND ISOMETRIC
 DRAWING AND PROVIDE INSTALLATION DETAILS.
  
 6) P0.1, P2.1, P5.1: PLEASE PROVIDE A SCHEDULE FOR THE
 REQUIRED BACKFLOW PREVENTERS TO BE INSTALLED ON SUPPLY
 LINES TO THE STERILIZERS, RO GENERATOR AND ALL OTHER
 PLUMBING FIXTURES PERFORMING A SPECIAL FUNCTION- SEE
 SECTIONS 422.2, 608.3, AND TABLE 608.1 FBC P. PLEASE
 SHOW THE BACKFLOW PREVENTER LOCATIONS ON THE PLUMBING
 PIPING PLANS AND ISOMETRIC DRAWING, AND PROVIDE AN
 INSTALLATION DETAIL.
  
 7) P0.1, P2.1, P5.1: SHOW THE LOCATIONS OF THE REQUIRED
 WATER HAMMER ARRESTORS FOR SUPPLY LINES TO FIXTURES AND
 EQUIPMENT WITH QUICK CLOSING VALVES- SECTION 604.9 FBC
 P.
  
 8) P0.1, P.2.1, P.51: PROVIDE ENLARGED WATER HEATER
 PIPING DETAILS SHOWING POTABLE WATER INLET AND OUTLET
 CONNECTIONS, PIPING CONNECTIONS TO RECIRCULATION PUMPS,
 BACKFLOW PREVENTERS- SECTION 502.1, 607.2, AND 608.3
 FBC P. PLEASE SHOW HOW STEAM CONDENSATION AND RELIEF
 VALVE DISCHARGE WILL BE DRAINED TO AN APPROVED LOCATION
 OR WASTE RECEPTOR-SECTION 314.2.1 AND 504.6 FBC P.
  
 9) P2.1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED
 TO THE LAVATORIES- SECTIONS 416.5 & 607.1.2 FBC P.
  
 10) P2.1 & P5.1: PLEASE LABEL THE HW & HWR LINES ON
 P2.1 & P5.1, AND THE RO SUPPLY AND RETURN LINES ON
 P5.1- SEE NOTE #11 AND SECTION 107.2.1 WPB.
  
 11) P5.1: PROVIDE THE CORRESPONDING TEXT FOR KEYNOTES
 12,13, & 14 SHOWN AT THE WATER HEATER/COMPRESSOR ROOM-
 SECTION 107.2.1 WPB.
  
 12) ROOF AND STORM DRAINS- FBC P.
  
 A) P2.0 & P2.2: PROVIDE A STORM DRAIN ISOMETRIC DRAWING
 SHOWING THE ROOF DRAIN VERTICAL LEADERS, UNDERSLAB
 HORIZONTAL STORM DRAINS, AND LOCATIONS OF REQUIRED
 CLEANOUTS- SECTIONS 1106.1, 1106.1, & 1108.1.
  
 B) P2.2: VERIFY THE ROOF AND DRAINAGE SYSTEM HAS BEEN
 DESIGNED IN COMPLIANCE WITH SECTION 1101.7 FOR MAXIMUM
 DEPTH OF PONDING WATER AND DEFLECTED STRUCTURAL
 ELEMENTS.
  
 C) P2.2: PLEASE SHOW THE PRIMARY AND OVERFLOW SCUPPERS
 THAT ARE SHOWN ON SHEET A3.1- SECTION 107.2.1 WPB AND
 1101.7.
  
 D) PROVIDE SIZING CALCULATIONS FOR THE PRIMARY VERTICAL
 LEADERS AND HORIZONTAL BRANCHES BASED ON SECTIONS
 1106.1 & 1106.2.
  
 E) PROVIDE SIZING CALCULATIONS FOR THE SECONDARY ROOF
 DRAINS- SECTION 1108.3.
  
 13) PROVIDE CIVIL PLANS SHOWING POINTS OF CONNECTIONS
 TO EXISTING SANITARY SEWER AND STORM DRAIN MAINS-
 SECTION 107.2.1 WPB.
  
 14) PROVIDE A PLUMBING SUB-PERMIT APPLICATIONS- SECTION
 105.1 WPB.
  
 15) PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTERS IN ACCORDANCE WITH SECTION 105.1
 WPB AND SEC, 90-33 WPB CODE OF ORDINANCES. THE DEVICE
 SHALL BE TESTED AND CERTIFIED BY THE WPB UTILITIES
 DEPARTMENT PRIOR TO FINAL INSPECTION BY THE BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT.AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719