2020-12-15 13:30:411ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110397
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS NEW ADDITION. FBC EC C403.2.1
  
 2) PLEASE PROVIDE A PROCEDURAL PROCESS DOCUMENT SHOWING
 THE PROCESS OF THE USE OF THIS SPACE. FBC 107.2.1
  
 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS. FBC M TABLE
 403.3.1.1
  
 4) PLEASE PROVIDE SPECS AS TO WHAT EF-1 AND EF-3 ARE
 EXHAUSTING AND CALCULATIONS AS TO THE CFM?S OF EACH
 EXHAUST FAN. ASHRAE 4.3.3
  
 5) PLEASE PROVIDE CALCULATIONS FOR TOTAL AIR CHANGES
 FOR EACH AREA. FBC M 407: ASHRAE-170 TABLE 7-1
  
 6) PLEASE SHOW PRESSURE RELATIONSHIP OF EACH SPACE TO
 ADJACENT AREAS. FBC M 407: ASHRAE 170 TABLE 7-1
  
 7) PLEASE SHOW THAT THE STEAMER MEETS SECTION 7.4.2 OF
 ASHRAE 170 FOR THE EXHAUST OF STEAM.
  
 8) PLEASE SHOW HOW THE AIR INTAKE FOR THE AHU MEETS
 RAIN ENTRAINMENT. FBC M 407: ASHRAE-170 6.2: ASHRAE
 62.1 5.5
  
 9) PLEASE SHOW ROOF ACCESS. FBC M 306.5
  
 10) PLEASE PROVIDE A COMPLETE LIST OF EQUIPMENT FOR
 THIS NEW ADDITION I.E. THE STEAMER FBC 107.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  