| 2020-12-15 13:30:41 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20110397 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS FOR THIS NEW ADDITION. FBC EC C403.2.1 |
| | |
| | 2) PLEASE PROVIDE A PROCEDURAL PROCESS DOCUMENT SHOWING |
| | THE PROCESS OF THE USE OF THIS SPACE. FBC 107.2.1 |
| | |
| | 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS. FBC M TABLE |
| | 403.3.1.1 |
| | |
| | 4) PLEASE PROVIDE SPECS AS TO WHAT EF-1 AND EF-3 ARE |
| | EXHAUSTING AND CALCULATIONS AS TO THE CFM?S OF EACH |
| | EXHAUST FAN. ASHRAE 4.3.3 |
| | |
| | 5) PLEASE PROVIDE CALCULATIONS FOR TOTAL AIR CHANGES |
| | FOR EACH AREA. FBC M 407: ASHRAE-170 TABLE 7-1 |
| | |
| | 6) PLEASE SHOW PRESSURE RELATIONSHIP OF EACH SPACE TO |
| | ADJACENT AREAS. FBC M 407: ASHRAE 170 TABLE 7-1 |
| | |
| | 7) PLEASE SHOW THAT THE STEAMER MEETS SECTION 7.4.2 OF |
| | ASHRAE 170 FOR THE EXHAUST OF STEAM. |
| | |
| | 8) PLEASE SHOW HOW THE AIR INTAKE FOR THE AHU MEETS |
| | RAIN ENTRAINMENT. FBC M 407: ASHRAE-170 6.2: ASHRAE |
| | 62.1 5.5 |
| | |
| | 9) PLEASE SHOW ROOF ACCESS. FBC M 306.5 |
| | |
| | 10) PLEASE PROVIDE A COMPLETE LIST OF EQUIPMENT FOR |
| | THIS NEW ADDITION I.E. THE STEAMER FBC 107.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |