| 2020-11-30 11:19:33 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20110397 |
| | ADD: 901 45TH ST. |
| | CONT: WESTBROOKE CORP. |
| | TEL: 561-395-4126 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV. 30TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) SHEET S-000 HEADING FOUNDATION INDICATES A SOILS |
| | REPORT BY ALTERRA ENGINEERING & TESTING, REPORT # |
| | 12-197. THIS SOILS TEST REPORT WAS SUBMITTED AND PAGE 4 |
| | OF 7 THERE WERE 3 PROVISIONAL PILE TYPE |
| | RECOMMENDATIONS. THEY WERE HELICAL PILE, CASED |
| | MICRO-PILES, & AUGER CAST PILE. SHEET S-000 UNDER THE |
| | HEADING OF FOUNDATION / PILES IT WOULD APPEAR THAT |
| | HELICAL PILE WILL BE INSTALLED. AT THE TIME OF THIS |
| | REVIEW THERE IS NO ADDITIONAL DOCUMENTATION THE ALTERRA |
| | WILL BE HIRED TO ENGAGE IN THE MONITORING OF THE |
| | INSTALLATION OF HELICAL PILE AND TO WHAT SERVICES |
| | ALTERRA WILL PERFORM. 2017 FBC-B 1810.3.1.5. HELICAL |
| | PILE. |
| | |
| | 2) SINCE THE CHOICE OF HELICAL PILE HAS BEEN MADE THERE |
| | WILL BE ADDITIONAL INFORMATION REQUIRED TO THE SOILS |
| | REPORT AS TO THE REQUIRED PILE CAPACITY AND THE |
| | REQUIRED DEPTH, ASSUMPTION TO MEET THE REQUIRED TONNAGE |
| | FOR FUTURE 4 STORY MEDICAL BUILDING ADDITION. 2017 |
| | FBC-B 1810.2. ANALYSIS. |
| | |
| | 3) STRUCTURAL SHEETS SHOW VARIOUS DETAILS WHERE FIELD |
| | WIELDING IS GOING TO TAKE PLACE DURING THE STRUCTURAL |
| | PHASE OF THE WORK PLEASE SHOW COMPLIANCE WITH: WELDED |
| | OR BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR |
| | FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY |
| | CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO |
| | BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |