2020-11-30 11:19:33WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110397
 ADD: 901 45TH ST.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 30TH/ 2020
 ACTION: DENIED
  
 1) SHEET S-000 HEADING FOUNDATION INDICATES A SOILS
 REPORT BY ALTERRA ENGINEERING & TESTING, REPORT #
 12-197. THIS SOILS TEST REPORT WAS SUBMITTED AND PAGE 4
 OF 7 THERE WERE 3 PROVISIONAL PILE TYPE
 RECOMMENDATIONS. THEY WERE HELICAL PILE, CASED
 MICRO-PILES, & AUGER CAST PILE. SHEET S-000 UNDER THE
 HEADING OF FOUNDATION / PILES IT WOULD APPEAR THAT
 HELICAL PILE WILL BE INSTALLED. AT THE TIME OF THIS
 REVIEW THERE IS NO ADDITIONAL DOCUMENTATION THE ALTERRA
 WILL BE HIRED TO ENGAGE IN THE MONITORING OF THE
 INSTALLATION OF HELICAL PILE AND TO WHAT SERVICES
 ALTERRA WILL PERFORM. 2017 FBC-B 1810.3.1.5. HELICAL
 PILE.
  
 2) SINCE THE CHOICE OF HELICAL PILE HAS BEEN MADE THERE
 WILL BE ADDITIONAL INFORMATION REQUIRED TO THE SOILS
 REPORT AS TO THE REQUIRED PILE CAPACITY AND THE
 REQUIRED DEPTH, ASSUMPTION TO MEET THE REQUIRED TONNAGE
 FOR FUTURE 4 STORY MEDICAL BUILDING ADDITION. 2017
 FBC-B 1810.2. ANALYSIS.
  
 3) STRUCTURAL SHEETS SHOW VARIOUS DETAILS WHERE FIELD
 WIELDING IS GOING TO TAKE PLACE DURING THE STRUCTURAL
 PHASE OF THE WORK PLEASE SHOW COMPLIANCE WITH: WELDED
 OR BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  