| 2020-11-23 10:46:42 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 4.6.7 BUILDING REHABILITATION. |
| | 4.6.7.1 REHABILITATION WORK ON EXISTING BUILDINGS SHALL |
| | BE |
| | CLASSIFIED AS ONE OF THE FOLLOWING WORK CATEGORIES IN |
| | ACCORDANCE |
| | WITH 43.2.2.1: |
| | (1) REPAIR |
| | (2) RENOVATION |
| | (3) MODIFICATION |
| | (4) RECONSTRUCTION |
| | (5) CHANGE OF USE OR OCCUPANCY CLASSIFICATION |
| | (6) ADDITION |
| | 4.6.7.2 REHABILITATION WORK ON EXISTING BUILDINGS SHALL |
| | COMPLY |
| | WITH CHAPTER 43. |
| | |
| | CHAPTER 43 BUILDING REHABILITATION |
| | |
| | 43.1.2 APPLICABLE REQUIREMENTS. |
| | 43.1.2.1 ANY BUILDING UNDERGOING REPAIR, RENOVATION, |
| | MODIFICATION, |
| | OR RECONSTRUCTION (SEE 43.2.2.1.1 THROUGH 43.2.2.1.4) |
| | SHALL COMPLY |
| | WITH BOTH OF THE FOLLOWING: |
| | (1) REQUIREMENTS OF THE APPLICABLE EXISTING OCCUPANCY |
| | CHAPTERS |
| | (SEE CHAPTERS 13, 15, 17, 19, 21, 23, 24, 26, 29, 31, |
| | 33, 37, |
| | 39, 40, AND 42) |
| | (2) REQUIREMENTS OF THE APPLICABLE SECTION OF THIS |
| | CHAPTER (SEE |
| | SECTIONS 43.3, 43.4, 43.5, AND 43.6) |
| | |
| | 1) THERE ARE NO INDICATIONS OF FIRE SPRINKLER |
| | PROTECTION. |
| | |
| | THE PROPOSED IS AN EXTENSION OF THE BUILDING WITH |
| | ASSEMBLY OCUPANCY AND FIRE SPRINKLER& FIRE ALARM |
| | PROTECTION IS REQUIRED TO BE EXTENDED INTO THE NEW |
| | SPACES. |
| | |
| | PLEASE REVIEW, CORRECT AND PROVIDE AN APPLICABLE NOTE |
| | OF ACKNOWLEDGEMENT |
| | |
| | |
| | 2) ANY FIRE SPRINKLER & FIRE ALARM WORK, INCLUDING |
| | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP |
| | DRAWINGS. |
| | |
| | PLEASE REVIEW, CORRECT AND PROVIDE AN APPLICABLE NOTE |
| | OF ACKNOWLEDGEMENT |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |