| 2020-11-20 15:51:18 | PATIO AWNINGS |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) SHOW THE SIGNAGE REQUIREMENT PER FBC 3105.5.3 |
| | STRUCTURES DESIGNED TO BE READILY REMOVED OR |
| | REPOSITIONED DURING PERIODS OF HIGH WIND VELOCITY SHALL |
| | BE POSTED WITH A LEGIBLE AND READILY VISIBLE DECAL OR |
| | PAINTED INSTRUCTIONS TO THE OWNER OR TENANT TO REMOVE |
| | OR REPOSITION THE STRUCTURE OR PART THEREOF DURING SUCH |
| | PERIODS OF TIME AS ARE DESIGNATED BY THE U.S. WEATHER |
| | BUREAU AS BEING A HURRICANE WARNING OR ALERT. |
| | 2) SHOW THE FIRE SPRINKLER REQUIREMENTS - YOUR ADDING A |
| | ROOFED AREA TO THE EXISTING SPRINKLERED FIRE AREA |
| | WITHOUT A FIRE BARRIER BETWEEN - FBC 202 FIRE AREA. THE |
| | AGGREGATE FLOOR AREA ENCLOSED AND BOUNDED BY FIRE |
| | WALLS, FIRE BARRIERS, EXTERIOR WALLS OR HORIZONTAL |
| | ASSEMBLIES OF A BUILDING. AREAS OF THE BUILDING NOT |
| | PROVIDED WITH SURROUNDING WALLS SHALL BE INCLUDED IN |
| | THE FIRE AREA IF SUCH AREAS ARE INCLUDED WITHIN THE |
| | HORIZONTAL PROJECTION OF THE ROOF OR FLOOR NEXT ABOVE. |
| | FBC 901.7 FIRE AREAS. WHERE BUILDINGS, OR PORTIONS |
| | THEREOF, ARE DIVIDED INTO FIRE AREAS SO AS NOT TO |
| | EXCEED THE LIMITS ESTABLISHED FOR REQUIRING A FIRE |
| | PROTECTION SYSTEM IN ACCORDANCE WITH THIS CHAPTER, SUCH |
| | FIRE AREAS SHALL BE SEPARATED BY FIRE BARRIERS |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR |
| | HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 711, OR BOTH, HAVING A FIRE-RESISTANCE RATING |
| | OF NOT LESS THAN THAT DETERMINED IN ACCORDANCE WITH |
| | SECTION 707.3.10. |
| | 3) THE STRUCTURAL CALCULATIONS PROVIDED DO NOT SHOW IN |
| | "ADOBE READER" AS ELECTRONICALLY SIGNED. |
| | 4) THE STRUCTURAL CALCULATIONS ARE SHOWING A WIND SPEED |
| | OF 45MPH SHOULDN'T THE WIND SPEED BE 170MPH. FBC 1609 |
| | |