| 2020-12-01 10:40:52 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20110373 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) I CANNOT DO A MECHANICAL REVIEW ON THIS PROJECT |
| | UNTIL A THE ITEMS BELOW ARE SUBMITTED. |
| | |
| | 2) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS |
| | PROJECT. FBC EC 101.5.1.1.2 |
| | |
| | 3) PLEASE PROVIDE THE MECHANICAL DRAWINGS SHOWING THE |
| | MECHANICAL SYSTEMS AND THE DUCT WORK. FBC 107.2.1 |
| | |
| | 4) PLEASE SHOW THE BATH EXHAUST FAN EXHAUST |
| | TERMINATIONS LOCATION. |
| | |
| | 5) PLEASE PROVIDE THE CONDENSATION PIPING AND LOCATION |
| | OF DISCHARGE. FBC RES 1411.3 |
| | |
| | 6) PLEASE SHOW THE LOCATION AND ANCHORAGE OF THE |
| | CONDENSING UNITS ON THE MECHANICAL DRAWING. FBC RES |
| | M1307.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |